ATEX Isolators Explained: How They Work & Why They’re Used

Published 16 Nov 2026

ATEX Zone 1 & Zone 2 Isolator – 3P+AUX – Craig & Derricott EXZ1SDR02530

ATEX isolators are electrical isolation devices designed for use in potentially explosive atmospheres. They allow electrical equipment and circuits to be disconnected from a power supply, helping engineers and maintenance personnel establish a safe working arrangement in hazardous-area installations.

Unlike ordinary industrial isolators, ATEX isolators incorporate explosion protection measures appropriate to their certified applications. These may include Ex d flameproof components, Ex e increased safety enclosures or a combination of protection concepts.

They are used in industries such as oil and gas, petrochemicals, chemical processing and industrial manufacturing, where equipment may be installed in hazardous-area Zones 1, 2, 21 or 22.

However, not all isolators perform the same electrical duties. Some are designed for off-load isolation, while switch-disconnectors are also rated to make and break specified electrical loads.

This guide explains what ATEX isolators are, how they work, the difference between isolators and switch-disconnectors, explosion protection methods, applications and important selection considerations.

Thorne & Derrick supply ATEX and IECEx certified hazardous-area isolators, including specialist solutions from Craig & Derricott and Eaton CEAG.


What Is an ATEX Isolator?

An ATEX isolator is an electrical isolating device incorporated into equipment designed for specified potentially explosive atmospheres. Its purpose is to provide an isolation function for an electrical circuit while meeting the applicable explosion protection requirements of the installation.

Depending on its electrical design, the device may be a disconnector or a switch-disconnector.

An isolator enables a circuit to be disconnected from its electrical supply, but the complete safe isolation procedure must also establish that the correct equipment has been isolated and that hazardous electrical energy is controlled.

ATEX certification addresses the equipment’s suitability for specified explosive atmospheres. It does not, by itself, establish the device’s complete electrical switching duty or replace electrical safe working procedures.

ATEX Isolators: Quick Facts

Main purpose: Provide electrical isolation in a suitably certified hazardous-area installation.

Explosion protection: May incorporate Ex d, Ex e or combined protection methods.

Typical locations: Certified installations in Zone 1, Zone 2, Zone 21 or Zone 22, subject to the individual equipment marking.

Electrical operation: Off-load disconnection or load switching, depending on the device’s utilisation category.

Common features: Rotary operating handles, padlocking arrangements, enclosure interlocks and durable industrial enclosures.

Typical equipment: Motors, pumps, ventilation systems, heaters and industrial machinery.


How Do ATEX Isolators Work?

ATEX isolators use a mechanical switching arrangement to separate the relevant electrical conductors from the supply.

Many industrial models feature a rotary handle mounted on the front of an enclosure. Turning the handle from ON to OFF operates the internal switching mechanism and opens the designated contacts.

The exact operation depends on the device construction, number of poles, electrical ratings and whether it is designed for off-load disconnection or load switching.

The Basic Operating Principle

  1. Normal operation: The isolating device is in its ON position, allowing the connected equipment to receive power.
  2. Isolation request: An authorised person follows the relevant electrical isolation procedure.
  3. Switch operation: The device is moved to OFF under conditions permitted by its electrical rating.
  4. Securing the device: A suitable lock-off arrangement may be applied to prevent unintended re-energisation.
  5. Verification: The necessary checks are completed to establish safe isolation before work begins.

Important: Moving a handle to OFF does not automatically prove that a circuit is safe to work on. Correct isolation, securing against reconnection and verification of absence of voltage must be carried out under the applicable safe working procedure.

Does an ATEX Isolator Protect Against Overload?

Not necessarily.

An isolator provides an isolation function, but it should not automatically be assumed to provide overcurrent, overload or short-circuit protection.

Those functions may be provided by separate protective equipment, such as correctly selected fuses, circuit breakers or motor protection devices.

The complete electrical system must be designed so that all necessary protection functions are provided.


Why Are ATEX Isolators Used in Hazardous Areas?

Electrical equipment installed in potentially explosive atmospheres must be designed and selected to control relevant ignition risks.

Ordinary electrical switching devices may contain contacts that generate arcs or sparks during operation. In a hazardous atmosphere, such ignition sources must be controlled through a suitable explosion protection concept.

An appropriately certified ATEX isolator combines the necessary electrical isolation or switching function with explosion protection suitable for its intended environment.

Three Important Functions

  • Electrical isolation: Enables an electrical circuit to be disconnected as part of a controlled maintenance or operational procedure.
  • Hazardous-area suitability: Incorporates appropriate protection measures for specified gas or dust atmospheres.
  • Operational control: Certain designs provide padlocking and interlocking arrangements to help manage access and prevent unintended operation.

These functions are particularly relevant where maintenance personnel need to isolate equipment located within classified production areas.


ATEX Isolator vs Switch vs Switch-Disconnector

One of the most important distinctions when specifying an ATEX isolator is the difference between an isolator, switch and switch-disconnector.

These terms describe different electrical duties. They should not be used interchangeably without checking the equipment’s technical ratings.

Electrical Switching Devices Compared
Device Main Function Key Consideration
Disconnector / Isolator Provides a defined electrical isolation function. An off-load disconnector must not be used to interrupt loads outside its rated duty.
Switch Makes and breaks electrical current within its rated switching duty. A switch is not necessarily suitable for an isolating function.
Switch-Disconnector Combines the specified switching function with an isolation function. Its rated utilisation category must suit the connected load.

What Is an Off-Load Isolator?

An off-load isolator is intended to provide isolation when the relevant load has already been removed or reduced to conditions permitted by the device’s rating.

It is not automatically suitable for interrupting a running motor or another substantial operating load.

What Is a Load-Break Switch-Disconnector?

A switch-disconnector is designed to perform both switching and isolation functions within its specified ratings.

Different utilisation categories cover different types of electrical duty, including resistive and inductive loads.

For example, a motor-related application may impose different switching requirements from a predominantly resistive heating circuit.

The manufacturer’s specified utilisation category must be checked before assuming the device can disconnect a particular load during normal operation.


ATEX Isolators vs Standard Industrial Isolators

Both ATEX and standard industrial isolators can provide electrical isolation functions. The main additional consideration for the ATEX equipment is certified suitability for the potentially explosive atmosphere.

ATEX vs Industrial Isolators
Feature ATEX Isolator Standard Industrial Isolator
Electrical Isolation Provided according to the device’s electrical characteristics. Provided according to the device’s electrical characteristics.
Explosion Protection Certified for specified potentially explosive atmospheres. Not inherently certified for explosive atmospheres.
Equipment Marking Includes relevant Ex certification and protection information. Normally uses conventional electrical and enclosure ratings.
Enclosure Construction must comply with the certified protection concept. Selected for conventional industrial electrical and environmental requirements.
Installation Requires compliance with applicable hazardous-area installation requirements. Requires compliance with applicable general electrical installation requirements.

An IP65 or IP66 enclosure rating alone does not make an isolator suitable for a hazardous area. Ingress protection describes resistance to dust and water ingress; it is not a substitute for explosion protection certification.


Ex d vs Ex e ATEX Isolators: What’s the Difference?

ATEX isolator assemblies may use different explosion protection concepts, depending on how the internal switching components, terminals and enclosure are designed.

Ex d – Flameproof Protection

Ex d is a flameproof protection concept in which a suitably designed enclosure can withstand an internal explosion and prevent flame transmission to the surrounding explosive atmosphere under its certified conditions.

Hazardous-area switchgear may use flameproof enclosures or components to manage potential ignition sources associated with electrical switching.

Ex e – Increased Safety Protection

Ex e uses additional construction measures intended to prevent ignition-capable sparks, arcs and excessive temperatures in the electrical parts to which this protection concept applies.

Some isolator assemblies combine an increased safety enclosure and terminal arrangement with flameproof switching components.

This is important because a product marketed as an Ex e isolator may carry a combined Ex d and Ex e marking, rather than using increased safety protection for every internal component.

Which Protection Concept Is Better?

Neither is universally better.

Selection depends on the certified assembly, installation requirements, equipment marking, electrical duty and environmental conditions.

Ex d and Ex e equipment should be compared using the manufacturer’s actual certification and construction details, rather than assuming all units within either category have identical characteristics.

For more technical background, see Ex d vs Ex e: Flameproof and Increased Safety Explained.


Which Hazardous Area Zones Require ATEX Isolators?

The required equipment protection level depends on the hazardous-area classification and the applicable gas or combustible dust atmosphere.

ATEX isolators are available with certification for specified hazardous areas, including Zones 1 and 2 for gases and Zones 21 and 22 for combustible dusts.

The suitability of a particular isolator must be verified using its complete equipment marking and certification documents.

Understanding Hazardous Area Zones
Zone Atmosphere General Description
Zone 1 Gas or vapour An explosive gas atmosphere is likely to occur occasionally during normal operation.
Zone 2 Gas or vapour An explosive gas atmosphere is not likely during normal operation and, if it occurs, persists only briefly.
Zone 21 Combustible dust An explosive dust atmosphere is likely to occur occasionally during normal operation.
Zone 22 Combustible dust An explosive dust atmosphere is not likely during normal operation and, if it occurs, persists only briefly.

Equipment must also be suitable for the relevant gas or dust group, temperature limitations and ambient conditions.

Explore the Hazardous Area Zones technical guide for further information.


Why Do ATEX Isolators Have Lockable Handles?

Many hazardous-area isolators include a rotary operating handle that can be padlocked in the OFF position.

This can support maintenance isolation procedures by helping prevent the device from being switched back ON unintentionally.

However, a lockable operating handle is only one element of an effective safe isolation procedure.

What Is a Door Interlock?

Some enclosed isolators incorporate mechanical interlocking between the switching mechanism and the enclosure lid.

The interlock may restrict enclosure access while the device is energised or in a specified switch position, depending on the product design.

Interlocking arrangements must be used as intended by the manufacturer and should not be bypassed outside approved procedures.

Is a Lockable Isolator the Same as an Emergency Stop?

No.

A lockable isolator and an emergency stop serve different safety functions.

An isolator provides a means of disconnecting a circuit, while an emergency stop is intended to initiate a specified stopping response when a hazardous event occurs.

The correct equipment depends on the relevant machinery, electrical and functional safety requirements.


Understanding ATEX Isolator Ratings

ATEX isolators are available in different electrical configurations. Selecting the correct product requires more than choosing a matching current rating.

Current Rating

The rated current identifies the level of current the device is designed to carry under its specified conditions.

For example, Craig & Derricott hazardous-area isolator ranges include different models with ratings such as 25A, 40A, 80A and higher, depending on the product family.

Actual electrical ratings must be checked against the particular catalogue number and the installation conditions.

Number of Poles

The pole configuration determines which conductors are switched or isolated.

Products may be available in three-pole, four-pole or other configurations, sometimes with auxiliary contacts.

The correct arrangement depends on the circuit design, earthing system and isolation requirements.

Utilisation Category

The utilisation category identifies the type of electrical switching duty for which the device is rated.

Different types of electrical load can impose different switching stresses.

A disconnector suitable for off-load isolation should not be assumed suitable for frequent load switching or motor interruption.

Temperature Class and Ambient Rating

Hazardous-area electrical equipment must remain within the temperature limitations specified by its certification.

The equipment’s temperature class or maximum surface temperature may depend on the product configuration and permitted ambient conditions.

This is particularly important when isolators are installed in warm industrial process environments.


Where Are ATEX Isolators Used?

Hazardous-area isolators are used in industrial electrical systems where equipment needs to be isolated locally and the installation presents a potentially explosive atmosphere.

Oil and Gas Installations

Potential applications include electrical isolation associated with pumps, motors, ventilation equipment and other plant installed in classified areas.

Chemical and Petrochemical Processing

ATEX isolators may be specified for equipment installed near processes involving flammable gases, vapours or liquids.

Industrial Heating Equipment

Some heating systems require a means of electrical isolation for inspection and maintenance.

Where the installation is within a classified hazardous area, the isolating equipment must have appropriate certification and electrical ratings.

Ventilation and Extraction Systems

Local isolation may be required for appropriately designed and certified ventilation equipment operating in industrial hazardous areas.

Dust-Handling and Processing Facilities

Combustible dust environments may require certified electrical equipment suitable for the applicable dust zone and material characteristics.

In all cases, the device must be selected as part of the complete electrical and hazardous-area installation design.


Craig & Derricott ATEX Isolators

Craig & Derricott manufacture specialist hazardous-area isolator and switch-disconnector assemblies used in industrial applications.

Thorne & Derrick supply Craig & Derricott products in different configurations, including models incorporating increased safety and flameproof protection concepts.

EXZ1 Series – Increased Safety Enclosures

The Craig & Derricott EXZ1 range includes isolator assemblies housed in glass reinforced polyester enclosures.

Selected products incorporate Ex d switching components and Ex e enclosure or terminal protection, with combined markings according to their certification.

Available features depend on the model and include rotary operating handles, OFF-position padlocking, interlocked enclosure arrangements and auxiliary contacts.

For example, the Craig & Derricott EXZ1SDR02530 is a 25A, three-pole-plus-auxiliary configuration listed by Thorne & Derrick for hazardous-area applications.

Explore the Ex e Hazardous Area Isolators range.

Ex d Flameproof Isolators

Craig & Derricott also offer hazardous-area isolator assemblies incorporating flameproof enclosure construction.

Options vary by model, including current rating, pole configuration, enclosure size and cable entries.

View Ex d Flameproof Isolators for product information and available configurations.

Note: Always verify the individual model’s current datasheet, certificate, permitted ambient range and electrical switching duty. Ratings and approvals cannot be assumed to apply across an entire product family.


How to Select the Correct ATEX Isolator

Choosing a hazardous-area isolator requires the electrical specification and explosion protection requirements to be assessed together.

ATEX Isolator Selection Checklist
Hazardous Area Confirm gas or dust zone, equipment group, EPL and temperature requirements.
Electrical Duty Determine whether off-load isolation or load switching is required.
Current and Voltage Check rated current, voltage and any applicable derating conditions.
Load Type Confirm the utilisation category is suitable for the connected equipment.
Pole Configuration Confirm the required number of poles and auxiliary contacts.
Explosion Protection Verify complete Ex marking, certificate and any special conditions for safe use.
Environmental Conditions Check ambient temperature, corrosion resistance and ingress protection.
Cable Entries Check gland compatibility, entry sizes and earthing arrangements.
Lock-Off Requirements Confirm padlocking, identification and required isolation procedures.

For product specifications and technical enquiries, view ATEX & IECEx Isolators supplied by Thorne & Derrick.


Common ATEX Isolator Selection Mistakes

1. Assuming Every Isolator Can Break Load Current

An off-load disconnector is not equivalent to a correctly rated load-break switch-disconnector.

Always check the device’s electrical switching duty and utilisation category.

2. Selecting Equipment by IP Rating Alone

IP ratings describe environmental ingress protection, not explosion protection suitability.

Hazardous-area equipment requires appropriate Ex certification and marking.

3. Ignoring the Complete Ex Marking

A device described as ATEX certified may have limitations relating to zones, gas groups, dust groups or ambient temperatures.

The complete marking and certificate must be checked.

4. Assuming OFF Means Safe to Work

The OFF position is not a substitute for a controlled isolation procedure and verification of absence of voltage.

5. Using Incorrect Cable Entries

Unsuitable cable glands, blanking elements or modifications may compromise the certified enclosure arrangement.

Use only suitable components and installation methods permitted by the equipment documentation.

Safety Note: Isolation of hazardous-area electrical equipment must be performed by competent personnel in accordance with approved site procedures. ATEX certification does not remove electrical shock, stored energy, arc flash or unexpected-start risks.

ATEX Isolators – Frequently Asked Questions

What is an ATEX isolator?

An ATEX isolator is an electrical isolation device incorporated into equipment certified for specified potentially explosive atmospheres. It provides an isolation function while using appropriate explosion protection measures for its intended installation.

How does an ATEX isolator work?

It operates a mechanical switching arrangement to disconnect designated conductors from an electrical supply. Many models use rotary handles and provide lock-off facilities. The permitted switching duty depends on the device rating.

What is the difference between an isolator and a switch-disconnector?

An isolator or disconnector provides an electrical isolation function. A switch-disconnector combines that function with a specified load-switching capability. Its utilisation category must suit the electrical load.

What is the difference between Ex d and Ex e isolators?

Ex d uses flameproof protection to contain an internal explosion, while Ex e uses increased safety measures in applicable electrical components. Some certified isolator assemblies combine both protection concepts.

Can ATEX isolators be used in Zone 1?

Yes, where the specific isolator assembly has equipment marking and certification suitable for the intended Zone 1 installation, including the relevant gas group and temperature requirements.

Are ATEX isolators suitable for Zone 21 and Zone 22?

Some ATEX isolators are certified for combustible dust environments. Suitability must be verified using the relevant dust equipment marking and the site’s hazardous-area classification.

Can an ATEX isolator be used as an emergency stop?

Not automatically. An isolator and an emergency stop have different functions. The safety system must be assessed and designed using suitable equipment for the required stopping and isolation functions.

Why are some ATEX isolators lockable?

Padlockable handles can help prevent unintended operation during controlled maintenance isolation. They do not replace the need to secure all relevant energy sources and verify safe isolation.

Are ATEX isolators available in different current ratings?

Yes. Manufacturers offer different rated currents, pole arrangements and electrical configurations. The correct device must be selected for the circuit, load and certified operating conditions.

Does ATEX certification mean an isolator is electrically safe for every application?

No. ATEX certification concerns suitability for specified explosive atmospheres. Electrical ratings, isolation capability, switching duty, circuit protection and safe working requirements must also be assessed.


Conclusion: Understanding ATEX Isolators

ATEX isolators provide electrical isolation functions in installations where appropriately certified equipment is required for potentially explosive atmospheres.

Understanding the difference between off-load isolators and switch-disconnectors is essential. The protection concept, current rating, utilisation category, enclosure construction and equipment certification must all suit the intended application.

For hazardous-area installations, Ex d and Ex e protection may be incorporated individually or as part of a combined certified assembly. Lockable handles and enclosure interlocks can also support controlled operating and maintenance procedures.

Thorne & Derrick supply a range of ATEX and IECEx hazardous-area isolators and switch-disconnectors, including solutions from Craig & Derricott and other specialist manufacturers.

Technical disclaimer: This article provides general guidance only. Equipment selection, installation and isolation must follow the latest applicable manufacturer documentation, product certification, electrical standards and site safety procedures.