ATEX Switch | Zone 1 Zone 2 Hazardous Area Ex d | ATX SWD016S300A

Zone 1 Zone 2 Switches ATEX | Ex d Hazardous Area Switch | ATX SWD

Zone 1 Zone 2 Switches ATEX | Ex d Hazardous Area Switch | ATX SWD

APPLETON ATX SWD016S300A

Product Category: Switches | ATEX Certified | Zone 1 & Zone 2 Hazardous Areas

Flameproof ATX SWD Series 16 and 32 Amp switches, circuit breakers and “break glass” call points manufactured by Appleton ATX are designed to prevent operation in explosive atmospheres during connect and disconnect operation of lighting and light power loads. The switches ideal for use in hazardous areas where ignitable vapors, gases or highly combustible dusts are present.

♦ See our complete range of ATEX Plugs for hazardous area electrical power distribution at low voltage – this includes flameproof plugs according to the Ex d Explosion Protection concept.

Full Range  ➡ Switches Hazardous Area Zone 1 Zone 2 ATEX Ex de

SWITCH Features

  • Flameproof. Ideal for installation in chemical and petrochemical plants, refineries and other hazardous area industries
  • Available up to 690 Volts and up to 32 Amps
  • Two threaded entries (one top and one bottom) M20 or M25
  • Switch mechanism fixed at the bottom of the box
  • Padlockable handle

ATEX SWITCH Specification

  • Switch Type: 3-pole switch
  • Entries: 2 x M20
  • Weight: 1.1kg  (2.43lbs)
  • Volume: 3.8 dm³ (231.89 in³)
  • Wiring Diagram Number: S300

SWD016S300A switch Specification Table

ATEX Certifications & Compliances Zone 1 and 2 – 21 and 22; Ex II 2 GD; IP66; IK10
Stand Materials Marine grade aluminum alloy box with A2 stainless steel captive screws
 Termination 16 Amp: 4 mm² (0.006 in²) terminals. 32 Amp: 6 mm² (0.009 in²) terminals
 Internal earth 2 x 4 mm² (0.006 in²) terminals
External earth 16 Amp: M5. 32 Amp: M6
 16 Amp Temperature Class T6 for Ta = +40 °C (+104 °F), T5 for Ta = +55 °C (+131 °F)
 16 Amp Surface Temperature T95 °C (+203 °F)
16 Amp Ambient Temperature 40 °C to +55 °C (-40 °F to +131 °F)
Hazardous Area Lighting Control Station Plug Junction Box

Lighting | Control Stations | Plugs & Sockets | Junction Boxes | Hazardous Area ATEX Certified Electrical Equipment for Explosive Atmospheres | Zone 1 & Zone 2

Data Sheets