Appleton ATX PRE432PR Plug | Ex de Increased Safety Plugs & Sockets

Zone 1 Zone 2 Plugs ATEX | Ex de Hazardous Area Plugs 16Amp & 32Amp | ATX PRE

Zone 1 Zone 2 Plugs ATEX | Ex de Hazardous Area Plugs 16Amp & 32Amp | ATX PRE

Increased Safety Plugs & Sockets| Ex de

ATEX | Zone 1 & 2 Hazardous Areas

Appleton ATX PRE432PR

ATX PRE Series 16 & 32 Amp Increased Safety plugs and sockets manufactured by Appleton ATX use a pin and sleeve design to deliver safe power to stationary and portable equipment in hazardous areas and those classed as Zone 1 and 2 and Zone 21 and 22. Suitable for use in damp, wet or corrosive environments, ATX PRE plugs and sockets are keyed and colour coded per IEC directives. The sockets are available in wall-mount, flush-mount and mobile versions.

♦ See complete range of ATEX Plugs for hazardous area electrical power distribution at LV – this includes flameproof plugs according to the Ex d Explosion Protection concept.

ATEX plug Specification

PRE432PR Increased Safety plug should be used in conjunction with ATX PRE432RR

plug Features

  • Plug and socket system is designed with a safe disconnect mechanism to insure maximum hazardous location protection
  • The contact separation is in a flameproof chamber
  • The automatic electrical disconnection of each phase is contained in a second flameproof chamber
  • Short circuit protection is 20 kA, while normal reference is 10 kA
  • Different voltages are color coded for easy identification
  • The receptacles are keyed to accept only ATX plugs (other plugs cannot be inserted)
  • ATX plugs can be used in non-hazardous IEC 309 sockets
  • Operating temperature of -40 °C to +55 °C (-40 °F to +131 °F)
  • Used With ATX PRE 32 Amp Increased Safety Plug – PRE432RR
  • See also Flameproof & Exd Enclosures

PRE432Pr plug Specification Table

Hazardous Area Classification
Zone 1 and 2 – Zones 21 and 22; Ex II 2 GD; IP66; IK09/10
Operating Temperature
-40 °C to +55 °C (-40 °F to +131 °F)
Voltage
20/25 Vac, 20/50 Vac, 40/50 Vac, 100/130 Vac, 200/250 Vac, 380/415 Vac, 480/500 Vac or 50/500 Vac
Number of Poles
2, 3
Number of Wires
3, 4, 5
Hertz
50/60 or 300 to 500 Hz
Materials and Finishes
Wall Socket for 2P – 2P+E – 3P is high impact resistance polycarbonate. Wall Socket for 3P+E – 3P+N+E: high impact resistance fiberglass reinforced polyester. Polyamide plug, mobile socket and flush socket.
Hazardous Area Lighting Control Station Plug Junction Box

Lighting | Control Stations | Plugs & Sockets | Junction Boxes | Hazardous Area ATEX Electrical Equipment | Increased Safety