EXHEAT FX-M Inline Encapsulated Thermostats – ATEX Certified Zone 1 & Zone 2

EXHEAT FX-M Inline Encapsulated Thermostats - ATEX Certified Zone 1 & Zone 2

EXHEAT FX-M Inline Encapsulated Thermostats – ATEX Certified Zone 1 & Zone 2

EXHEAT FX-M

Inline Encapsulated Thermostats

Zone 1 & Zone 2 (IIA, IIB, IIC) Hazardous Areas

EXHEAT FXT-M inline encapsulated thermostats have been established as temperature control solution where space is at a premium with the capability of changing small and medium sized heaters to be able to retain a pre-determined ambient temperature.

The FXT-M is composed of a unique electronic potting compound, stainless steel shroud and polyolefin sheath. Robust and lightweight in design a main benefit of the thermostat is it requires minimal maintenance.

Similar to the FXT-DR and FXT-DI thermostats the FXT-M can be linked with the FX hazardous area compact enclosure heaters designed specifically for frost protection, anti-condensation and temperature control – operating in ambient temperatures up to +80°C.

Alternatively, when supplied with up to 10m of cable, the FXT-M can be installed to control any electrical item inside a cabinet or enclosure.

:arrow:Please contact T&D in order to check your specification and consider the correct duty necessary for your installation.

  • Certification: ATEX/IECEx II 2 G D
    EXHEAT

    EXHEAT Stockist – Worldwide Delivery, Competitive Quotations

    Ex mb IIC T6 to T5 Gb
    Ex mb IIIC T85°C to T100°C Db
    CU TR (EAC)
    CU-TR.012/2011 CERTIFIED 1 Ex db IIC T6…T3 Gb X
    Ex tb IIIC T85°C…T200°C Db X
    CSA
    Class I Div 2, Groups A, B C and D T6…T5
    Class III, Div 2: Class II Div 2, Groups E, F & G.
    Class I, Zone 1, AEx db IIC T6…T4 Class III, Zone 21:
    Type 4 Ex mb IIC T6…T4 Gb Ex mb IIIC T85°C..T135°C Db IP66

  • Protection Method: Encapsulated
  • Voltage: 110 to 277VAC
  • Ambient Temperature: -50°C to +80°C
  • Temperature Class: T5 (T100°C) to T6 (T85°C). T5 and T6 thermostats are suitable for use in T1 to T4 (T450°C to T135°C)
    hazardous environments. Ensure ambient temperature limits are adhered to
  • Cable: 3M standard (up to 10M available on request)
  • Ingress Protection: IP66
FXT-M Encapsulated Inline Thermostats

FXT-M Encapsulated Inline Thermostats

Inline Encapsulated Thermostats

Applications

  • Acoustic enclosures
  • Condensation prevention
  • Control/monitoring panels
  • Control valve housings
  • Fire hose cabinets
  • Frost protection
  • Generators
  • Instrumentation cabinets
  • Manifolds
  • Motor enclosures/cabinets
  • Valve blocks
FXT-M Inline Encapsulated Thermostats - Dimensions

FXT-M Inline Encapsulated Thermostats – Dimensions

FXT-M

Inline Encapsulated Thermostats

Specification

EXHEAT Part NumberOpen / Close
Temperature (+/-3°C)
VoltageMax
Current
Temp
Class
Max
Ambient
Weight
FXT-M-516°C / 5°C110-120V
220-240V
254-277V
6.0 A
3.3 A
4.8 A
T6
T5
60°C
80°C
0.1kg
FXT-M-2026°C / 15°C
FXT-M-4037°C / 26°C
FXT-M-6069°C / 58°C9.0 A

HAZARDOUS AREA ELECTRICAL, MECHANICAL, PROCESS & INSTRUMENTATION SPECIALISTS

Thorne & Derrick International distribute Electrical, Mechanical, Process & Instrumentation Equipment to the global hazardous area industries and are approved vendors to most leading oil, gas and petrochemical companies and their EPC’s.

T&D supply ATEX & IECEx Certified equipment for the detection, metering, flow measurement and heat tracing of potentially explosive gases in hazardous areas Zone 1 and Zone 2.

Hazardous Area - Gas Detection, Metering, Lighting & Flow Measurement

 

➡ Did you know? T&D have a dedicated Exports and Hazardous Area Sales Team, send an enquiry.

➡ Did you know? T&D are Thermon, The Heat Tracing Specialists, largest UK stockist.

➡ Did you know? T&D are Trained by Crowcon in the specification and sale of Gas Detectors.