Chromalox HSRL 3-1CT 3W/FT 120V Trace Heating Cables
Trace Heating Cables
Chromalox HSRL 3-1CT hazardous area trace heating cables are self regulating and provide process temperature maintenance and frost protection to pipework, instrument lines, tanks and drums up to 65º Celsius – with CSA and FM certification Chromalox HSRL heat trace cables ensures operating integrity in Div. 1 hazardous areas.
- Manufacturer: Chromalox
- Heating Cable Range: HSRL
- Heating Cable Code: HSRL 3-1CT
- Maximum Maintain Temperature : 65° Celsius
- Maximum Continuous Exposure Temperature : Power Off 85° Celsius
- Cable Type: Self Regulating, Energy Efficient Trace Heating Cables
- Cable Ratings: 3 Watts Per Foot @ 50°F
- Cable Voltage: 120V
- Maximum Heating Cable Circuit Length: Up to 360 feet
- Minimum Cable Bend Radius : 1-1/8″
- Weight/1000′: 66 lbs
- See Also: Trace Heating
Trace Heating Cable
Construction
- Twin 16 AWG Copper Buss Wires are able to Provide reliable electrical current capability.
- Semiconductive Polymer Core Matrix is the ‘self regulating component of the cable and it’s electrical resistance varies with temperature.
- Polyolefin Jacket is flame retardant and electrically insulates the matric and buss wires and provides resistance to water and some inorganic chemical solutions.
- Tinned Copper Braid that provides additional mechanical protection in any environment, and a positive ground path.
- High Temperature Fluoropolymer Overjacket is a corrosion resistant, flame retardant overjacket is highly effective in many environments.
Maximum Circuit Lengths in Feet
Maximum Cable Circuit Length (Ft.) by Start-Up Temperature (°F) and Breaker Size (Amps) |
||
Heating Cable Rating | HSRL 3-1CT Trace Heating | |
50°F Start-Up (Ft.) Circuit Breaker |
10 A | 205 |
15 A | 305 | |
20 A | 360 | |
25 A | NR | |
30 A | NR | |
40 A | NR | |
0°F Start-Up (Ft.) Circuit Breaker |
10 A | 135 |
15 A | 200 | |
20 A | 270 | |
25 A | 330 | |
30 A | 360 | |
40 A | NR | |
-20°F Start-Up (Ft.) Circuit Breaker |
10 A | 120 |
15 A | 185 | |
20 A | 245 | |
25 A | 300 | |
30 A | 360 | |
40 A | NR |
Hazardous Area Approvals
FM Approvals
- Class I, Division 1, Groups B, C, D
- Class II, Division 1, Groups E, F, G
- Class III, Division 1
- 3 Watt rated T6 temperature class
- 5 and 8 Watt rated T5 temperature class
- 10 Watt rated T4A temperature class
CSA
- Class I, Division 1, Groups B, C, D
- Class II, Division 1, Groups E, F, G
- 3 Watt rated T6 temperature class
- 5 and 8 Watt rated T5 temperature class
- 10 Watt rated T4A temperature class
➡ See also : Electrical Heating for Hazardous Areas