The F200 by Craig & Derricott is a range of fire rated isolators designed for installations where the LV electrical supply must be maintained for 2 hours at 200°C in the event of a fire. The isolators range from from 20A to 200A, these electrical isolation units are supplied in IP66/65 die-cast aluminium or IP65 sheet steel enclosures.

Fire rated isolators (switch disconnectors) are installed throughout industrial, building services and HVAC (ventilation fans) projects providing excellent switching ability even under fire conditions.

F200 fire resistant isolators (often referred to as switch disconnectors) are mounted near to the extraction fan for isolation purposes and have been tested in conjunction with the fan equipment to meet the strict thermal requirements of BS EN 12101-3.

BS EN 12101-3 Standard | Smoke & Heat Control Systems. Specification for powered smoke and heat control ventilators (Fans).

All isolators are supplied in a Traffic Red (RAL 3020) polyester powder coat finish, with padlocking in both ‘Off’ and ‘On’ positions.

Isolator Options

‘N’ = switched neutral (Early make, late break) | ‘NL’ = Unswitched neutral | ‘EB = Early break auxiliary contacts
‘T’= Increased terminal capacity

F200 Fire Resistant IsolatorsFP200

The below table shows all variations of the F200 range of fire resistant isolators including the rating, format, switch type, enclosure material and colour as well as the IP rating.

Isolator Rating Format Switch Type C&D Part No Encl. Size Encl. Material IP Rating Encl. Colour
20A 6P GX20 F2SDDR206 A Die-CastAluminium IP66 Traffic Red Ral 3020
6P+2EB Aux F2SDDR206EB
25A 2P CS25 F2SDDR252 A Die-CastAluminium IP66 Traffic Red Ral 3020
3P F2SDDR253
3P+2EB Aux F2SDDR253EB
3P+N F2SDDR253N
3P+NL F2SDDR253NL
32A 2P CS32 F2SDDR322 A Die-CastAluminium IP66 Traffic Red Ral 3020
3P F2SDDR323
3P+2EB Aux F2SDDR323EB
3P+N F2SDDR323N
3P+NL F2SDDR323NL
2P F2SDDR402 Die-CastAluminium IP66 Traffic Red Ral 3020
3P CS40R F2SDDR403 A
3P+2EB Aux F2SDDR403EB
3P+N F2SDDR403N
3P+NL F2SDDR403NL
40A 6 P GX40 F2SDDR406 IP65
6P+2 EB Aux F2SDDR406EB
2 P F2SDDR402T
3P CS40 F2SDDR403T B
3P+2EB Aux F2SDDR403EBT
3P+N F2SDDR403NT
3P+NL F2SDDR403NLT
63A 2P CS63 F2SDDR632 B Die-CastAluminium IP65 Traffic Red Ral 3020
3P F2SDDR633
3P+2EB Aux F2SDDR633EB
3P+N F2SDDR633N
3P+NL F2SDDR633NL
80A 3P CS80 F2SDDR803 B Die-CastAluminium IP65 Traffic Red Ral 3020
3P+N F2SDDR803N
3P+NL F2SDDR803NL
63A 3P+N CS63 F2SDRC00633N 1 Sheet Steel IP65 Traffic Red Ral 3020
3P+NL F2SDRC00633NL
6P F2SDRC00636 2
80A 3P+N CS80 F2SDRC00803N 1 Sheet Steel IP65 Traffic Red Ral 3020
3P+NL F2SDRC00803NL
6P F2SDRC00806 2
100A 3P+N CS100 F2SDRC01003N 3A Sheet Steel IP65 Traffic Red Ral 3020
3P+NL F2SDRC01003NL
125A 3P+N CS125 F2SDRC01253N 4A Sheet Steel IP65 Traffic Red Ral 3020
3P+NL F2SDRC01253NL
160A 3P+N CS160 F2SDRC01603N 4A Sheet Steel IP65 Traffic Red Ral 3020
3P+NL F2SDRC01603NL
200A 3P+N CS200 F2SDRC02003N 5A Sheet Steel IP65 Traffic Red Ral 3020

Technical Specification – Fire Rated

Data supplied against tests to IEC/BS EN 60947-3.

F200  – Isolators & Switch-Disconnectors (O-I)
Application Sym. Unit Category 20A 25A 32A 40A 63A 80A 100A 125A 160A 200A
Switch product range GX20 CS25 CS32 GX40 CS40 CS4 0R CS63 CS80 CS100 CS125 CS160 CS200
Rated thermal current Ithe A 20 25 32 40 40 40 63 80 100 125 160 200
Rated insulation voltage Ui V 690 690 690 690 690 69 0 690 690 1000 1000 1000 1000
Rated impulse voltage Uimp kV 6 6 6 6 6 6 6 6 8 8 8 8
Rated operational power (3 phase AC) kW 380 / 440 – AC23 7.5 11 15 18.5 18.5 15 25 30 59 63 75 75
690V – AC23 7.5 15 15 15 22 15 30 30 51 55 55 55
Rated short time withstand current (1 sec) Icw A 250 500 600 800 1100 60 0 1300 1400 2600 2800 3000 3000
Max. fuse size for short circuit protection (gG Characteristic) kA 10kA 20 35 35 40 80 40 80 80 160 160 160 200
25kA 16 32 35 35 80 32 63 63 160 160 160 160
50kA 32 32 80 32 63 63 160 160 160 160
Recommended connecting capacity mm2 Flexible cable 2.5 x 2 6 6 6 x 2 16 6 16 16 25 50 50 70
mm2 Rigid cable 2.5 x 2 10 10 10 x 2 25 10 25 25 50 70 70 95
Nm Tightening torque 1.0 1.2 1.2 1.0 1.2 1.2 1.2 1.2 2/ 5 2/ 5 2/ 5 12
Fire Resistant Isolators | F200 Dimensions

Fire Resistant Isolators | F200 Dimensions

Rating Cable Entries
Enclosure A Enclosure B Enclosure C
Top Bottom Top Bottom Top Bottom
20A – 32A 2 x M20 2x M25
40A 2x M25 2x M25 + 1x M20 2x M20
63A 2x M25 + 1x M20
80A 2x M32 + 1x M20

Fire Rated Isolators – F200 Enclosed Switch-Disconnectors

Fire Rated - F200 Enclosed Switch-Disconnectors

Fire Rated – F200 Enclosed Switch-Disconnectors

 

Encl. Size H W D A B C Ø E F G J Ø Ø
1 250 250 100 170 170 40 6.5 35 53 18 58 6.5
2 250 300 200 170 220 67 6.5 35 58 18 58 6.5
3A 350 300 175 270 220 67 8.5 35 58 13 58 8.5
4A 400 300 175 320 220 67 8.5 35 58 13 58 8.5
5 550 450 250 470 370 67 8.5 35 58 13 58 8.5
5A 550 400 175 470 320 67 8.5 35 58 13 58 8.5
6 750 450 275 670 370 67 8.5 35 58 13 58 8.5
7 750 600 300 670 520 67 8.5 35 58 13 58 8.5
8 900 600 300 820 520 67 10.5 35 58 13 58 10.5
9 900 600 400 820 520 67 10.5 35 58 13 58 10.5

External Mounting Feet (Four per set)
Enclosure Sizes 1 & 2Cat No. SEFL1/KIT