Fire Rated Isolators | F200 Fire Resistant Isolators | Switch Disconnectors

Fire Rated Isolators | F200 Fire Resistant Switch Disconnectors | 2 Hours at 200°C
F200 Fire Resistant Switch Disconnectors
Fire Rated Isolators
The F200 by Craig & Derricott is a range of fire rated isolators designed for installations where the LV electrical supply must be maintained for 2 hours at 200°C in the event of a fire. The isolators range from from 20A to 200A, these electrical isolation units are supplied in IP66/65 die-cast aluminium or IP65 sheet steel enclosures.
Fire rated isolators (switch disconnectors) are installed throughout industrial, building services and HVAC (ventilation fans) projects providing excellent switching ability even under fire conditions.
F200 fire resistant isolators (often referred to as switch disconnectors) are mounted near to the extraction fan for isolation purposes and have been tested in conjunction with the fan equipment to meet the strict thermal requirements of BS EN 12101-3.
♦ BS EN 12101-3 Standard | Smoke & Heat Control Systems. Specification for powered smoke and heat control ventilators (Fans).
All isolators are supplied in a Traffic Red (RAL 3020) polyester powder coat finish, with padlocking in both ‘Off’ and ‘On’ positions.
Isolator Options
‘N’ = switched neutral (Early make, late break) | ‘NL’ = Unswitched neutral | ‘EB = Early break auxiliary contacts
‘T’= Increased terminal capacity
F200 Fire Resistant Isolators
The below table shows all variations of the F200 range of fire resistant isolators including the rating, format, switch type, enclosure material and colour as well as the IP rating.
Isolator Rating | Format | Switch Type | C&D Part No | Encl. Size | Encl. Material | IP Rating | Encl. Colour | |
20A | 6P | GX20 | F2SDDR206 | A | Die-CastAluminium | IP66 | Traffic Red Ral 3020 | |
6P+2EB Aux | F2SDDR206EB | |||||||
25A | 2P | CS25 | F2SDDR252 | A | Die-CastAluminium | IP66 | Traffic Red Ral 3020 | |
3P | F2SDDR253 | |||||||
3P+2EB Aux | F2SDDR253EB | |||||||
3P+N | F2SDDR253N | |||||||
3P+NL | F2SDDR253NL | |||||||
32A | 2P | CS32 | F2SDDR322 | A | Die-CastAluminium | IP66 | Traffic Red Ral 3020 | |
3P | F2SDDR323 | |||||||
3P+2EB Aux | F2SDDR323EB | |||||||
3P+N | F2SDDR323N | |||||||
3P+NL | F2SDDR323NL | |||||||
2P | F2SDDR402 | Die-CastAluminium | IP66 | Traffic Red Ral 3020 | ||||
3P | CS40R | F2SDDR403 | A | |||||
3P+2EB Aux | F2SDDR403EB | |||||||
3P+N | F2SDDR403N | |||||||
3P+NL | F2SDDR403NL | |||||||
40A | 6 | P | GX40 | F2SDDR406 | IP65 | |||
6P+2 | EB Aux | F2SDDR406EB | ||||||
2 | P | F2SDDR402T | ||||||
3P | CS40 | F2SDDR403T | B | |||||
3P+2EB Aux | F2SDDR403EBT | |||||||
3P+N | F2SDDR403NT | |||||||
3P+NL | F2SDDR403NLT | |||||||
63A | 2P | CS63 | F2SDDR632 | B | Die-CastAluminium | IP65 | Traffic Red Ral 3020 | |
3P | F2SDDR633 | |||||||
3P+2EB Aux | F2SDDR633EB | |||||||
3P+N | F2SDDR633N | |||||||
3P+NL | F2SDDR633NL | |||||||
80A | 3P | CS80 | F2SDDR803 | B | Die-CastAluminium | IP65 | Traffic Red Ral 3020 | |
3P+N | F2SDDR803N | |||||||
3P+NL | F2SDDR803NL | |||||||
63A | 3P+N | CS63 | F2SDRC00633N | 1 | Sheet Steel | IP65 | Traffic Red Ral 3020 | |
3P+NL | F2SDRC00633NL | |||||||
6P | F2SDRC00636 | 2 | ||||||
80A | 3P+N | CS80 | F2SDRC00803N | 1 | Sheet Steel | IP65 | Traffic Red Ral 3020 | |
3P+NL | F2SDRC00803NL | |||||||
6P | F2SDRC00806 | 2 | ||||||
100A | 3P+N | CS100 | F2SDRC01003N | 3A | Sheet Steel | IP65 | Traffic Red Ral 3020 | |
3P+NL | F2SDRC01003NL | |||||||
125A | 3P+N | CS125 | F2SDRC01253N | 4A | Sheet Steel | IP65 | Traffic Red Ral 3020 | |
3P+NL | F2SDRC01253NL | |||||||
160A | 3P+N | CS160 | F2SDRC01603N | 4A | Sheet Steel | IP65 | Traffic Red Ral 3020 | |
3P+NL | F2SDRC01603NL | |||||||
200A | 3P+N | CS200 | F2SDRC02003N | 5A | Sheet Steel | IP65 | Traffic Red Ral 3020 |
Technical Specification – Fire Rated
Data supplied against tests to IEC/BS EN 60947-3.
F200Â – Isolators & Switch-Disconnectors (O-I) | |||||||||||||||||||||||||||||||||
Application | Sym. | Unit | Category | 20A | 25A | 32A | 40A | 63A | 80A | 100A | 125A | 160A | 200A | ||||||||||||||||||||
Switch product range | – | – | GX20 | CS25 | CS32 | GX40 | CS40 | CS4 | 0R | CS63 | CS80 | CS100 | CS125 | CS160 | CS200 | ||||||||||||||||||
Rated thermal current | Ithe | A | 20 | 25 | 32 | 40 | 40 | 40 | 63 | 80 | 100 | 125 | 160 | 200 | |||||||||||||||||||
Rated insulation voltage | Ui | V | 690 | 690 | 690 | 690 | 690 | 69 | 0 | 690 | 690 | 1000 | 1000 | 1000 | 1000 | ||||||||||||||||||
Rated impulse voltage | Uimp | kV | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 8 | 8 | 8 | 8 | |||||||||||||||||||
Rated operational power (3 phase AC) | kW | 380 / 440 – AC23 | 7.5 | 11 | 15 | 18.5 | 18.5 | 15 | 25 | 30 | 59 | 63 | 75 | 75 | |||||||||||||||||||
690V – AC23 | 7.5 | 15 | 15 | 15 | 22 | 15 | 30 | 30 | 51 | 55 | 55 | 55 | |||||||||||||||||||||
Rated short time withstand current (1 sec) | Icw | A | 250 | 500 | 600 | 800 | 1100 | 60 | 0 | 1300 | 1400 | 2600 | 2800 | 3000 | 3000 | ||||||||||||||||||
Max. fuse size for short circuit protection (gG Characteristic) | kA | 10kA | 20 | 35 | 35 | 40 | 80 | 40 | 80 | 80 | 160 | 160 | 160 | 200 | |||||||||||||||||||
25kA | 16 | 32 | 35 | 35 | 80 | 32 | 63 | 63 | 160 | 160 | 160 | 160 | |||||||||||||||||||||
50kA | – | 32 | 32 | – | 80 | 32 | 63 | 63 | 160 | 160 | 160 | 160 | |||||||||||||||||||||
Recommended connecting capacity | mm2 | Flexible cable | 2.5 x 2 | 6 | 6 | 6 x 2 | 16 | 6 | 16 | 16 | 25 | 50 | 50 | 70 | |||||||||||||||||||
mm2 | Rigid cable | 2.5 x 2 | 10 | 10 | 10 x 2 | 25 | 10 | 25 | 25 | 50 | 70 | 70 | 95 | ||||||||||||||||||||
Nm | Tightening torque | 1.0 | 1.2 | 1.2 | 1.0 | 1.2 | 1.2 | 1.2 | 1.2 | 2/ 5 | 2/ 5 | 2/ 5 | 12 |

Fire Resistant Isolators | F200 Dimensions
Rating | Cable Entries | |||||
Enclosure A | Enclosure B | Enclosure C | ||||
Top | Bottom | Top | Bottom | Top | Bottom | |
20A – 32A | — | 2 x M20 | — | — | — | 2x M25 |
40A | — | 2x M25 | — | 2x M25 + 1x M20 | — | 2x M20 |
63A | — | — | — | 2x M25 + 1x M20 | — | — |
80A | — | — | — | 2x M32 + 1x M20 | — | — |
Fire Rated Isolators – F200 Enclosed Switch-Disconnectors

Fire Rated – F200 Enclosed Switch-Disconnectors
Encl. Size | H | W | D | A | B | C | Ø | E | F | G | J | Ø Ø |
1 | 250 | 250 | 100 | 170 | 170 | 40 | 6.5 | 35 | 53 | 18 | 58 | 6.5 |
2 | 250 | 300 | 200 | 170 | 220 | 67 | 6.5 | 35 | 58 | 18 | 58 | 6.5 |
3A | 350 | 300 | 175 | 270 | 220 | 67 | 8.5 | 35 | 58 | 13 | 58 | 8.5 |
4A | 400 | 300 | 175 | 320 | 220 | 67 | 8.5 | 35 | 58 | 13 | 58 | 8.5 |
5 | 550 | 450 | 250 | 470 | 370 | 67 | 8.5 | 35 | 58 | 13 | 58 | 8.5 |
5A | 550 | 400 | 175 | 470 | 320 | 67 | 8.5 | 35 | 58 | 13 | 58 | 8.5 |
6 | 750 | 450 | 275 | 670 | 370 | 67 | 8.5 | 35 | 58 | 13 | 58 | 8.5 |
7 | 750 | 600 | 300 | 670 | 520 | 67 | 8.5 | 35 | 58 | 13 | 58 | 8.5 |
8 | 900 | 600 | 300 | 820 | 520 | 67 | 10.5 | 35 | 58 | 13 | 58 | 10.5 |
9 | 900 | 600 | 400 | 820 | 520 | 67 | 10.5 | 35 | 58 | 13 | 58 | 10.5 |
External Mounting Feet (Four per set)
Enclosure Sizes 1 & 2Cat No. SEFL1/KIT
Enclosure Sizes 3 – 7 Cat No. SEFL2/KIT
Enclosure Sizes 8 – 10Cat No. SEFL3/KIT
âž¡ Related Products | Fire Rated Resistant Junction Boxes Enclosures | Fire Rated Resistant Plugs

Fire Rated Isolators | F200 | F300 | F400 for Fire Resistant Building Services Applications

Fire Resistant Isolators | ATEX Explosion Proof Hazardous Area Zone 1 & Zone 2