Ex de Lighting – Explosion Proof Hazardous Area Technor LED EV Wellglass Lighting

Ex de Lighting – Explosion Proof Hazardous Area Technor LED EV Wellglass Lighting
ZONE 1, ZONE 21 LED Wellglass LIGHTING
EXPLOSION PROTECTION EX de
LED Wellglass Lighting for Zone 1, Zone 21, Zone 2, Zone 22 Hazardous Area Lighting Applications
Thorne & Derrick, the Specialist Distributors of Hazardous Area Lighting can provide competitive prices and supply from stock the complete range of Technor products including electrical enclosures and junction boxes.
Technor’s LED EV is a wellglass Ex de lighting fixture suitable for hazardous area lighting and offers offers Ex-e IIC mode of protection and provide high illumination without causing dazzling or light pollution.
Technor LED EV wellglass lighting is classified to international hazardous area classifications with ATEX, IECEx and TRCU certification, with ingress protection IP66 and an operational ambient temperature range of -52°C to +60°C.
LED EV are especially resistant to shock or vibration and are also free from infrared and ultraviolet wavelengths.
Technor LED EV Wellglass Lighting – Technical Features
Material | Aluminium with low content of copper |
IP rating | IP66 |
Ambient temperature range | -52°C to +60°C |
Approvals |
INERIS 01ATEX0019X (standard)
IECEx INE 15.0031X
CoC TR CU 012/2011 (marking upon request, ordering code to be required)
|
Gaskets | O-ring made of Nitrile Rubber (NBR) |
Surface treatment | Green colour polyurethane painting cycle RAL6003 (other colour available upon request) |
Entries | N° 2 entries M25x1,5 (plugs and cable glands excluded) |
Hardware and screws | AISI304 Stainless steel external hardware and screws |
Lamps | Included |
Rated Operation Voltage (UE) | 115/240V, 24Vdc |
Frequency | 50 Hz / 60 Hz |
Technor LED EV Lighting
Technor Part Number | Code | Lamp (W) | Weight (Kg) | Temperature Class | Dimensions (mm) | Voltage | |||
A | B | C | D | ||||||
EVDE-3/LED 18 | A04713118181D | 18 | 6.00 | T4* | 547 | 333 | 214 | 195 | 115/240V 50/60Hz |
EVDE-3/LED 18 | A04713118191D | 18 | 6.00 | T4* | 547 | 333 | 214 | 195 | 24VDC |
* In case of maximum ambient temperature reaches +40°C, temperature class changes into T5 (ordering code to be required)

Explosion Proof Hazardous Area Technor LED EV Wellglass Lighting – Dimensions
HAZARDOUS AREA CERTIFICATION & MARKING FOR Lighting
ATEX
- II 2 GD
- Ex de IIC T(**) Gb
- Ex tb IIIC T(**) Db IP66
- ** T5/T100°C, T4/T135°C
under IEC Ex directive, junction boxes and enclosures are suitable for IIC group of gases/dusts onlyÂ
Approvals
Certified 01ATEX0019X (standard), IECEx INE 15.0031X, CoC TR CU 012/2011 (marking upon request, ordering code to be required)