Chromalox CWM 8-1C 8W/FT 120V Trace Heating Cables

chromalox-cwm-constant-wattage-trace-heating-cable-to-392f-200-c

Trace Heating Cables

  • Manufacturer: Chromalox
  • Heating Cable Range: CWM
  • Heating Cable Code: CWM 8-1C 8W/FT 120V
  • Cable Type: Constant Wattage, Medium Temperature
  • Circuit Load: 0.067 Amps/Ft.
  • Cable Voltage: 120V
  • Output Wattage at 120V: 8 W/Ft.
  • Maximum Heating Cable Circuit Length:  290 Ft.
  • Length Between Nodes: 36″
  • Approximate Cable Size: 0.30″W x 0.25″H
  • Minimum Cable Bend Radius: 1-1/4″
  • Heating Cable Maximum Exposure Temperature: Power Off, 392°F  (200°C)
  • See Also: Trace Heating

CWM trace heating cables manufactured by Chromalox, including CWM 8-1C provide frost protection to pipework and valves, tanks and associated mechanical services – suitable for hazardous area zones including Div 2. For use on metallic pipes only.

Heating Cable Applications

  • Process Pipework Maintenance
  • Frost Protection of Pipework
  • Fluid Flow, Transfer & Viscosity Maintenance

Cable Ordering Information

Output (W/Ft.) Nominal Voltage (Vac) Model Description Wt./1000′ (Lbs.) Chromalox Order Code
8 120 CWM 8-1C Standard tinned-copper metallic braid for additional  protection and ground path 96 392139
CWM 8-1CT Fluoropolymer corrosion resistant overjacket over braid for hostile or corrosive environments 110 392163

  1. Twin 12 AWG Copper Buss Wires – Provide reliable, consistent electrical current
  2. FEP Insulation Jacket Electrically insulates buss wires
  3. Pairing Jacket Secures two buss wires together and provides wrapping surface for Nichrome wire
  4. Nickel Chromium Wire – Cable heating component
  5. FEP InsulationRugged outer sheath protects heating cable, assures longer service life, and provides protection against environmental application hazards
  6. Tinned Copper Braid – Plated copper braid increases robust construction, provides ground path and provides additional protection in any location (suffix “C” in model number)
  7. FEP – Fluoropolymer overjacket, over the braid, provides protection from most aqueous and chemically corrosive solutions (suffix “T” in model number) – ideal for trace heating systems installed in hazardous areas with explosive atmospheres

Hazardous Area Approvals

UL Listed for ordinary areas.

CSA Certified for ordinary and:

  • Class I, Div. 2, Groups A, B, C, D
  • Class II, Div. 2, Groups F, G. Rated T3 Temperature Class (Exception: Cable surface temperature shall not exceed 190°C in Class II, Div. 2, Group F; 165°C in Class II, Div. 2, Group G)

➡ See also : Electrical Heating for Hazardous Areas