ATEX Hazardous Area Plastic Control Stations Zone 1 & 21 – Abtech PCS
Abtech PCS hazardous area control stations are ATEX Certified for use in Zone 1 and Zone 21 hazardous areas.
- Area Classification Zone 1 & 21, Gas & Dust
- Type of Protection Controller with Ammeter only: Ex e (Increased Safety), Controller with Switches & Indicator Lamps: Ex de (flameproof & increased safety)
- Apparatus Coding Ex e II T6, Ex tD A21 IP66 T800 C Ex de IIC T6, Ex tD A21 IP66 T800 C
- Certificate Number DNV 12 ATEX 13746
Plastic Control Stations
Zone 1 & Zone 21 Hazardous Areas Application
Abtech PCS control stations are suitable for both industrial and hazardous areas and have been designed for use in potentially explosive atmospheres and are suitable for most gas groups including hydrogen.
Protection Degree IP66 to EN60529.
Abtech PCS Control Stations
Configuration Options
Part Reference | Control Station
Dimensions HxWxD (mm) |
Fixing Centres (mm) Horizontal/Vertical | Maximum Populations | ||
Operators | Ammeters | Both | |||
Abtech PCS01 | 86 x 95 x 76 | 73 / 58 | 1 x Op | N/A | N/A |
Abtech PCS02 | 86 x 135 x 76 | 73 / 98 | 2 x Op | 1 x Am | N/A |
Abtech PCS03 | 86 x 175 x 76 | 73 / 138 | 3 x Op | N/A | 1 x Op, 1 x Am |
Abtech PCS06 | 100 x 215 x76 | 88 / 150 | 4 x Op | N/A | 2 x Op, 1 x Am |
See Abtech data sheet for typical layout drawings.
Abtech PCS control stations, manufactured from plastic are suitable for Zone 1 and Zone 21 hazardous areas according to the ATEX Directive – the PCS is available with a selection of different manufacturers operators and indicators.
Control Stations – Zone 1 & Zone 21 Hazardous Area ATEX
Maximum Cable Entries
Max Cable Entries* | Control Station Top Side (A) | Control Station Bottom Side (C) | ||||
M20 | M25 | M32 | M20 | M25 | M32 | |
PCS01 | 1 | 1 | N/A | 1 | 1 | N/A |
PCS02 | 1 | 1 | N/A | 1 | 1 | N/A |
PCS03 | 1 | 1 | N/A | 1 | 1 | N/A |
PCS06 | 2 | 2 | 1 | 2 | 2 | 1 |
Electrical Data
Operator Type | Push Button, Emergency Stop, Mushroom Head, Key Release Push Button | |||
Utilization Category | AC12 | AC15 | DC13 | DC13 |
Max Rated Voltage | 250V | 250V | 110V | 24V |
Max Rated Current | 16A | 10A | 0.5A | 1A |
Operator Type | Indicator Lamp | |||
Utilization Category | AC15 | DC13 | ||
Max Rated Voltage | 250V | 24V | ||
Max Rated Current | 6A | 1A | ||
Operator Type | Illuminated Push Button | |||
Utilization Category | AC15 | DC13 | ||
Max Rated Voltage | 240V | 24V | ||
Max Rated Current | 6A | 1A |
Temperature Rating
Max ambient range: ‐40 ºC to +40 ºC
Abtech PCS – Ordering Information