ATEX Hazardous Area Plastic Control Stations Zone 1 & 21 – Abtech PCS

Abtech PCS Plastic Control StationsAbtech PCS hazardous area control stations are ATEX Certified for use in Zone 1 and Zone 21 hazardous areas.

  • Area Classification  Zone 1 & 21, Gas & Dust
  • Type of Protection  Controller with Ammeter only: Ex e (Increased Safety),   Controller with Switches & Indicator Lamps: Ex de (flameproof & increased safety)
  • Apparatus Coding  Ex e II T6, Ex tD A21 IP66 T800 C  Ex de IIC T6, Ex tD A21 IP66 T800 C
  • Certificate Number  DNV 12 ATEX 13746

Plastic Control Stations

Zone 1 & Zone 21 Hazardous Areas Application

Abtech PCS control stations are suitable for both industrial and hazardous areas and have been designed for use in potentially explosive atmospheres and are suitable for most gas groups including hydrogen.

Protection Degree IP66 to EN60529.

Abtech PCS Control Stations

Configuration Options

Part Reference Control Station

Dimensions HxWxD (mm)

Fixing Centres (mm)  Horizontal/Vertical  Maximum Populations
Operators Ammeters Both
Abtech PCS01 86 x 95 x 76 73 / 58 1 x Op N/A N/A
Abtech PCS02  86 x 135 x 76 73 / 98 2 x Op  1 x Am N/A
Abtech PCS03 86 x 175 x 76 73 / 138 3 x Op N/A 1 x Op, 1 x Am
Abtech PCS06 100 x 215 x76 88 / 150 4 x Op N/A  2 x Op, 1 x Am

See Abtech data sheet for typical layout drawings.

Abtech PCS control stations, manufactured from plastic are suitable for Zone 1 and Zone 21 hazardous areas according to the ATEX Directive – the PCS is available with a selection of different manufacturers operators and indicators.

Control Stations – Zone 1 & Zone 21 Hazardous Area ATEX

Control Stations – Zone 1 & Zone 21 Hazardous Area ATEX

Maximum Cable Entries

 Max Cable Entries*   Control Station Top Side (A)  Control Station Bottom Side (C) 
M20 M25 M32 M20 M25 M32
PCS01 1 1 N/A 1 1 N/A
PCS02 1 1 N/A 1 1 N/A
PCS03 1 1 N/A 1 1 N/A
PCS06 2 2 1 2 2 1

 Electrical Data

Operator Type Push Button, Emergency Stop, Mushroom Head, Key Release Push Button
Utilization Category AC12 AC15 DC13 DC13
Max Rated Voltage 250V 250V 110V 24V
Max Rated Current 16A 10A 0.5A 1A
Operator Type Indicator Lamp
Utilization Category AC15 DC13
Max Rated Voltage 250V 24V
Max Rated Current 6A 1A
Operator Type Illuminated Push Button
Utilization Category AC15 DC13
Max Rated Voltage 240V 24V
Max Rated Current 6A 1A

Temperature Rating

Max ambient range: ‐40 ºC to +40 ºC

Abtech PCS - Ordering Information

Abtech PCS – Ordering Information

ATEX Hazardous Area Plastic Control Stations Zone 1 & 21 - Abtech PCS

ATEX Hazardous Area Plastic Control Stations Zone 1 & 21 – Abtech PCS

Abtech PCS Control Stations

T&D Are Main Abtech Stockists: Hazardous Area Power, Control & Instrumentation Junction Boxes & Electrical Enclosures suitable for low voltage and high voltage (3.3kV, 6.6kV, 11kV, 33kV) networks.

 

Data Sheets