Marechal DS2 Plugs, Sockets & Decontactors 250A 1000V (AC22 AC23)
plugs & sockets 250A
Marechal DS2 | Credit back to this page for use.
marechal ds2
The DS2 Plugs and Sockets, designed by Marechal offer have a rated current of 250A and a maximum voltage of 1000V. Marechal DS2 Decontactors, Plugs & Sockets are IP66/IP67, regardless of whether the plug is connected or the protection lid is closed.
The Marechal DS Plugs & Sockets have an incorporated breaking capacity of AC-22 / AC-23 and have an impact resistant metal casing. Marechal’s DS2 Industrial Plug also features a shock resistance rating of IK10 which means the decontactors are protected against 20 joules of impact or the equivalent to the impact of a 5 kg mass dropped from 400 mm above the impacted surface.
A “Decontactor” Plug & Socket, typically used in industrial settings/hazardous areas (ATEX & IECEx), features an integrated power switch for safe connection and disconnection of electrical equipment. The integrated load-break switch, allows for safe disconnection when under a full load, which is crucial when carrying out maintenance or repairs. The socket outlet installation is designed to be completely safe, with no risk of electrical hazards, guaranteeing operating speed and time efficiency.
Marechal DS2 Plugs
Technical Specification
Marechal DS2 Plugs, Sockets & Decontactors Technical Specification | |
Rated Current (with wiring according to standard) | 250A |
Maximum Voltage | 1000V |
IP Protection Lid Closed | IP66/IP67 |
IP Protection Connected Plug | IP66/IP67 |
Shock Resistance | IK10 |
Ambient Temperature | -40ºC to +60ºC |
Flexible Wiring (Min-Max) | 70 mm² – 95 mm² |
Stranded Wiring (Min-Max) | 70 mm² – 120 mm² |
Other Wiring | On Request |
Keying Positions | 12 |
Load Break Capability of Marechal DS2 Decontactor
- Comply with IEC EN 60309-1 and IEC EN 60309-4 standards – (250 A / 500 V) or (200 A / 690 V)
- Load-break capability according to IEC EN 60947-3 / AC-22A – (250 A / 400 V) or (125 A / 690 V)
- Load-break capability according to IEC EN 60947-3 / AC-23A – 160 A / 440 V
- Short-circuit current Icc – 10 kA
Marechal DS2 Socket Outlets & Inlets
A full range of boxes, sleeves, handles, adaptors and accessories can also be supplied. Part of the Marechal ATEX Plugs, Sockets & Connectors complete collection, the Marechal DS range of plugs and sockets are suitable for rated currents from 30A up to 400A and maximum voltages from 690V up to 1000V.
Voltage 50Hz | Polarity | Marechal DS2 Socket Outlet (Female) 250A | Marechal DS2 Inlet (Male) 250A |
380-440V AC | 3P+E | 3924013 | 3928013 |
220-250V AC / 380-440V AC* | 3P+N+E | 3924017 | 3928017 |
660-690V AC | 3P+E | 3924193 | 3928193 |
380-440V AC / 660-690V AC* | 3P+N+E | 3924197 | 3928197 |
1000V AC | 3P+E | 3924223 | 3928223 |
*Dual-voltage socket outlet
Power Distribution & Control In Hazardous Areas
T&D also distribute hazardous area isolators, control panels and distribution boards, electrical enclosures and motor starters certified according to ATEX for use in Zone 1 & Zone 2 (gas/vapour) explosive atmospheres.