Zone 1 Intrinsically Safe LED Panel Hazardous Area ATEX IECEx Ex i – Abtech Nimbus
Zone 1 Intrinsically Safe LED Panel Hazardous Area ATEX IECEx Ex i – Abtech Nimbus
The Abtech Nimbus is a low profile LED panel fully ATEX and IECEx certified for use in Zone 1 hazardous areas. The Zone 1 LED Panel provides a significant weight and energy saving over a traditional recessed fluorescent.
The low glare panel design of the intrinsically safe LED panel provides excellent uniformity and colour rendering, replicating the light output of fluorescent luminaires. The Abtech Nimbus is available in pure white (5700K) or warm white (2700K) giving installers more flexibility and the ability to match colour temperature to individual applications. This makes the Nimbus ideal for installation in control rooms, corridors and offshore accommodation modules. The panel also has an in-built push to dim facility.
To protect against the rigors of offshore installation, the Nimbus control gear has been designed with harmonic and overvoltage protection to prevent damage to the LEDs.
Installation of the Nimbus panel could not be simpler via M3 mounting studs. Panels are flush mounted as standard and are intended to sit below, rather than replace ceiling tiles. This ensures that ceiling integrity is maintained, particularly important for SOLAS B-15 fire rated installations.
The driver unit for the panel can be installed up to four metres away, allowing it to be conveniently located and save space in the ceiling void. The connection between the panel and driver is via a flame retardant LSZH cable and features a plug & socket connection for easy installation.
Zone 1 Intrinsically Safe LED Panel Hazardous Area ATEX IECEx Ex i – Abtech Nimbus
Zone 1 Intrinsically Safe LED Panel Hazardous Area Ex i
Features
- Excellent uniformity and colour rendering
- Dimmable (Push to dim)
- Emergency version with battery status/fault condition indicator and automatic self-testing
- Plug & socket connection between panel and driver for easy installation
- 5-year complete system warranty*
Luminaire Type | LED panel luminaire |
Ingress Protection | IP44 Panel, IP66 Driver to EN60529 |
Material | Panel: Aluminium frame, PMMA diffuser / Driver: Aluminium enclosure |
Lamp Type | Light emitting diode, pure white (5700K) |
LED Life | 50,000 hours L70 @ 25°C |
Colour Rendering Index | CRI 80 |
Installation Connections | 4m flying lead from driver to panel. Cable is fire retardant LSZH to IEC 60331-21 & 31, IEC 60754-1 and IEC 61034-2 |
Control Gear | Remote HF electronic driver with harmonic protection BS 61000-4-2, 3, 4, 5, 6, 8, 11 and EN 55024, heavy industry level, criteria A. Overvoltage up to 3kVAC. |
Dimming | Push to dim: 100% > 75% > 50% > Off |
Mounting | Via removable 40mm M4 studs secured on to back plate |
Supply | 90V to 264V 50/60Hz ac |
Emergency Duration | 90 minutes at 50% output or 180 minutes at 25% output |
Battery | 6V 4.5Ah Ni-Cd |
Abtech Nimbus Zone 1 Lighting
Luminaire Ratings
Abtech Product Reference | Lamp Type |
Dimensions (mm) |
Power (W) |
Lumen Output | Ambient Temperature |
LX1NIM05LB57 | LED | 150 x 150 | 13W | 730 | -20°C to 40°C |
LX1NIM11LB57 | LED | 300 x 300 | 17W | 1,460 | -20°C to 40°C |
LX1NIM125LB57 | LED | 275 x 600 | 20W | 2,100 | -20°C to 40°C |
LX1NIM12LB57 | LED | 300 x 600 | 20W | 2,100 | -20°C to 40°C |
HAZARDOUS AREA CERTIFICATION
Abtech Nimbus intrinsically safe LED panel are certified according to leading hazardous area classifications including:
- Area Classification Zone 1, Gas
- Type of Protection Panel – Ex ib (intrinsically safe)
Driver – Ex eb ib q (increased safety, intrinsically safe, sand filled) - Apparatus Coding Panel – Ex ib IIB T4 Gb
Driver – Ex eb [ib Gb] qb IIB T4 Gb - Certificate Number CML 16ATEX3026X / IECEx CML 16.0020X
T&D, The Explosive Atmosphere Experts, provide a single-source capability for the most extensive range of Electrical, Mechanical, Process & Instrumentation Equipment suitable for hazardous area locations.
Zone 1 Intrinsically Safe LED Panel Abtech Nimbus – Dimensions
Abtech Nimbus – Options
LB27 | Warm white (2700K) |
E90 | 90-minute emergency duration (90 minutes at 50% output) |
DS | Dark Start, allows inhibition of battery for use on un-manned platforms |
NST | Non self-test emergency version |
RAL9016 | White panel frame (RAL9016) |
FM60 | 60mm long flush M4 mount studs with backing plate for insulated tile mounting |
Add the required suffix to the product reference.
Example: LX1NIM05LB27 = Zone 1, 13W panel with warm white (2700K) LEDs