Hazardous Area Thermostats | Flameproof Transmitter Enclosures Zone 1 Zone 2 | EXHEAT HIH

EXHEAT Hazardous Area Thermostats ATEX & IECEx
ATEX Thermostats | Â Zone 1 or 2 (IIA, IIB, IIC) Zone 21 or 22 (IIIA, IIIB, IIIC)
Hazardous Area Thermostats
ATEX Certified
EXHEATÂ HIH hazardous area thermostats are designed to accommodate most makes of head mounted process transmitter or termination block providing hazardous area certified heating and air warming
The range of HIH instrument enclosures manufactured by EXHEAT are certified for use in hazardous areas where the atmosphere is classified as a Zone 1 or 2 (IIA, IIB, IIC) Gas Group, or a Zone 21 or 22 (IIIA, IIIB, IIIC) Dust Group explosive atmosphere according to ATEX Directive.

EXHEAT HIH Hazardous Area Thermostats
Features of EXHEAT HIH Hazardous Area Thermostats
- Ingress protection – ATEX thermostats are IP66
- Enclosure – 316 stainless steel
- Optional viewing window for transmitter LCD displays
- Cable – M20 cable entries (2 standard, 4 maximum)
- Temperature Range – hazardous area thermostats suitable for ambient temperatures from -50°C to +60°C
EXHEAT HIH Hazardous Area Thermostat
ATEX Certification
Certification: ATEX Equipment Directive and IECEx

Hazardous Area Thermostats For Zone 1 Zone 2 Hazardous Area
 II 2 G/D Ex d IIC T6 (Gas) Ex tD A21 T85°C (Dust)
Certified to meet the ATEX Equipment Directive and IECEx   II 2 G/D Ex d IIC T6 (Gas) Ex tD A21 T85°C (Dust)
CU TR (EAC) certified
Installation – Exheat HIH
- The instrument housing should be securely fixed in position using the M8 side mountings or
with the wall brackets supplied - All terminal connections of the hazardous area thermostat should be checked for tightness before energising
- At no time is this equipment to be used outside its approved ambient temperature range of – 50°C to +60°C (this may be restricted further by the limitations of the transmitter (where fitted) – refer to the transmitter certificate where applicable
Enclosure | 316 stainless steel enclosure –Â Ingress protection IP66 |
---|---|
Cable Entries | M20 cable entries (2 standard, 4 maximum) |
Option | Optional viewing window for transmitter LCD displays |
Ambient Temperature | -50°C to +60°C |

EXHEAT Stockist – Worldwide Delivery, Competitive Quotations
EXHEAT HIH Hazardous Area Thermostat
Applications
- Temperature measurement and display for all applications
- Accommodates all major brands of head mounted process transmitter
- Hazardous area process temperature measurement
- Thermowell assemblies available
- Machinery and plant construction, power engineering, heating, ventilation, and refrigeration

Air Heaters | Immersion Heaters | Line Heaters | Thermostats | ATEX & IECEX Certified Electrical Heaters
T&D – Experts in Equipment for Explosive Atmospheres
Trust Thorne & Derrick to specify and supply from stock safe and reliable Heat, Light & Power Products for use in hazardous area locations and explosive atmospheres certified to international standards including ATEX and IECEx – this includes Zone 1 / Zone 2 (Flammable Gas) or Zone 21 / Zone 22 (Dusts) and Class I, Division 1 and Division 2 hazardous area requirements.
Since 1985 as Leaders in ATEX Innovation we can facilitate succession planning for the replacement of obsolete, non-conformant and legacy equipment – we are the provider of innovative solutions to ensure ATEX and IECEx Compliance for Electrical, HVAC & Process Instrumentation systems in the explosive atmosphere industries.