Hazloc Heaters XET1-1-E-A Electronic Explosionproof Thermostat – ATEX, IECEx & EAC Ex
Hazloc Heaters XET1-1-E-A Electronic Explosionproof Thermostat
Hazloc XET1-1-E-A is an electronic thermostat for heating applications only including unit and convection hazardous area heaters requiring a 24VAC control with an IP66 rating and suitable for a hydrogen gas atmosphere (Zone Group IIB+H2) – XET1
The hazardous area thermostat has a temperature adjustment range of 5°C to 25°C, is extremely rugged, has a very fast acting electronic temperature sensor that is unaffected by altitude, dial locking screw to prevent unwanted adjustments, a contact-free switching mechanism that is not susceptible to wear, EMC compliance that guarantees no nuisance tripping, two (3/4”NPT) openings for easy field wiring and its non-orientation sensitivity allows for mounting in any position.
Hazloc XET1-1-E-A has an aluminium and 304 stainless steel construction with no exposed copper or brass provides suitability for H2S environments.
ATEX, IECEx & EAC Ex Thermostat
Hazloc Heaters XET1-1-E-A
Explosionproof Thermostat Features
- Bolted, removable cover provides instant access for installation and servicing
- Dial locking screw prevents unwanted adjustments
- Phenolic thermal-break standoffs between knob & base prevents heat creep
- IP66 rating for moisture/dust protection
- CFC & mercury free, no levelling required
- Contact-free switching mechanism is not susceptible to wear
- Fast-acting, accurate, bi-metal sensing plate is unaffected by altitude
- Completely sealed design is ideal for dusty environments
- Vibration resistant design prevents setpoint drift
- Two (3/4″ NPT) openings for easy field wiring (includes one 3/4″ plug)
- Non-orientation sensitivity allows for mounting in any position
- Low profile design allows easy access in confined spaces
- EMC compliance guarantees no nuisance tripping
Hazloc Heaters XET1-1-E-A
Specification
Temperature adjustment range | 5°C to 25°C (40°F to 80°F) |
Temperature differential | +/- 1°C (1.8°F) from set point |
Operating limits | -50°C (58°F) ≤ T amb ≤ +40°C (104°F) |
Storage limits | -50°C to +60°C (-58°F to +140°F) |
Switching | Electronic |
Field wiring openings | Two 3/4″ NPT (includes one 3/4″ plug) |
Ingress protection | IP66 |
Net weight | 1.4 Kg |
Ship weight | 1.5 Kg |
Shipping dimensions | 12.7 cm x 12.7 cm x 17.8 cm |
Hazardous Area Approvals & Protection Methods
- CE 0518 II 2G Ex db IIB+H2 T6 Gb (ATEX)
- Ex db IIB+H2 T6 Gb (IECEx)
- 1ExdIIBT6 /H2 (EAC Ex)
- -50°C ≤ T amb ≤ +40°C, IP66
(Gas Atmosphere Certified for ATEX / IECEx / EAC Ex Zone 1 and 2) - CE 0518 II 2D Ex tb IIIC T85°C Db (ATEX)
- Ex tb IIIC T85°C Db (IECEx)
- Ex tb IIIC T85°C Db X (EAC Ex)
- -50°C ≤ T amb ≤ +40°C, IP66
(Dust Atmosphere Certified for ATEX / IECEx / EAC Ex Zone 21 and 22) - ATEX/IECEx:
General requirements IEC/EN 60079-0
Flameproof IEC/EN 60079-1
Dust ignition proof IEC/EN 60079-31 - EAC Ex:
Hazardous location TR CU 012/2011
EMC TR CU 020/2011 - Ingress protection:
IEC 60529
Hazloc Heaters XET1-1-E-A – Physical Dimensions
Hazloc heaters | HEATING APPLICATIONS
Hazloc Heaters are global suppliers and manufacturers of industrial and explosion-proof heaters and thermostats for hazardous areas and severe duty locations – this includes industrial heating products for non-hazardous and severe-duty applications. Explosion proof and hazardous area certifications include North American (NEC & CE), International (CENELEC & IEC), European (ATEX) and Russian EAEU (EAC EX).