ATEX Control & Distribution Units Hazardous Area Zone 1 & Zone 2 Junction Box Ex d – Eaton MEDC SM87JB

ATEX Control & Distribution Units Zone 1 & Zone 2 Junction Box Ex d – Eaton MEDC SM87JB Hazardous Area Control & Distribution Units
ATEX Control & Distribution Units
Zone 1 & Zone 2
Eaton MEDC SM87JB are ATEX control & distribution junction boxes for applications in ATEX & IECEx Zone 1 and Zone 2 hazardous areas. The hazardous area control & distribution units are available in stainless steel or marine grade alloy. Various terminals and entries can be accommodated.
Stainless steel, one of the most durable materials available on the market, is both hard wearing and corrosion resistant, increasing the life of products in harsh environments and therefore reducing maintenance costs.

Eaton MEDC SM87JB
ATEX Detectors, Control & Distribution Units
Zone 1 & Zone 2
ATEXFeatures
- Zone 1 and Zone 2 use.
- Ex d IIC T5/T6
- ATEX approved Ex II 2GD
- IECEx certified Gb, Db.
- IP66 & IP67
- Optional telephone or relay initiate
- Optional resistors or diodes

Eaton MEDC SM87JB – Dimensions
MEDC SM87JB Hazardous Area Control & Distribution Units
Technical Specification
Hazardous Area Certification | |
ATEX Ex d | Cert. no. Bas03ATEX0463. Certified to: EN60079-0, EN60079-1, EN60079-31. Ex II 2GD, Ex d IIC T4/5/6 Gb, Ex tb IIIC T135/100/85°C Db, IP66/67 |
IECEx Ex d | Cert. no. IECEx BAS 13.0048 Certified to: IEC60079-0, IEC60079-1, IEC60079-31. Ex d IIC T4/5/6 Gb, Ex tb IIIC T135/100/85°C Db, IP66/67 |
Specifications | |
Material | Stainless steel grade 316 ANC4B, marine grade alloy LM25 |
Finish | Painted to customer specification |
Certified temp | -55°C to +85°C (T4) -55°C to +70°C (T5) -55°C to +55°C (T6) T ratings are for units with terminals only |
Weight | 3.1kg |
Ingress protection | IP66 and IP67 |
Entries | Max. one per face in M20 or M25 ISO |
Resistor or diode | Contact sales office for information. Maximum of two components |
Relay initiate | Initiate voltage: 24 or 48Vdc Max switching voltage: 250Vac Max switching current: 10A |
Telephone initiate | Ringing voltage: 24-70Vac Max switching voltage: 240Vac Max switching current: 2A |
EATON MEDC SM87JB – ORDERING REQUIREMENTS
The following code is designed to help in selection of the correct Eaton hazardous area control & distribution unit with ATEX approval and certification. Build up the part number by inserting the code for each component into the appropriate box.

Eaton SM87JB – Ordering Requirements

ATEX Detectors, Control & Distribution Units
High Voltage Electrical Equipment
To support the safe and reliable distribution of Medium & High Voltage Electricity in industrial non-hazardous and hazardous area locations, Thorne & Derrick distribute a complete range of MV HV Electrical Connectors, Joints & Terminations including ATEX Certified variants for installation in Zone 1 & Zone 2 explosive atmospheres.