Flameproof Wellglass Fluorescent Light Fittings | Hazardous Area Zone 1 2 21 22 | ATX LDP Series

Appleton ATX LDP Series Wellglass Luminaires

Flameproof wellglass

Hazardous Area Lighting

Zone 1 & Zone 2 (21 & 22)

ATEX & IECEX Certified

Product Category: Hazardous Area Lighting | Fluorescent Light Fittings

Flameproof ATX LDP Series compact fluorescent Wellglass light fittings, manufactured by Appleton ATXare designed for a variety of lamp types. These flameproof fixtures are an ideal hazardous area lighting option for street lighting on refinery sites and oil depots or for tank lighting purposes, as well as hazardous locations such as plants where plastics, paints, thinners and petrochemicals are manufactured.

FEATURES

  • E27 lampholder (lamps are not supplied)
  • The lamps are available in the following lamp types: 18 to 25 Watts compact fluorescent lamps; 70 to 150 Watts halogen lamps; Up to 200 Watts incandescent lamps; Up to 160 Watts mixed lamps
  • Threaded flame path
  • Suspension is via integrated eye bolt for side cable entry versions; use with blanking plug (provided)
  • The flameproof Wellglass light fittings are supplied with one blanking plug for side cable entry versions
  • Connection to lampholder: 2 x 2.5 mm² (0.0039 in²) or to terminal block: 2 x 2.5 mm² (0.0039 in²) supplied for through-wiring application

SPECIFICATIONS

  • Standard Materials and Finishes: Grey painted, marine grade aluminum alloy body and bezel with aluminum internal reflector
  • ATEX Certifications & Compliances: Zone 1 and 2 – 21 and 22; Ex II 2 GD; IP66; IK08
  • Specific Wattages: 18 Watts Compact Fluorescent; 20 W Compact Fluorescent; 25 Watts Compact Fluorescent; 100 Watts Incandescent; 200 Watts Incandescent; 70 Watts Halogen; 150 Watts Halogen; 160 Watts Mixed
  • Ambient Temperature: -40 °C to +55 °C (-40 °F to +131 °F)

LDP2M20

FLAMEPROOF wellglass LIGHT FITTINGS

COMPACT FLUORESCENT

Appleton ATX LDP2M20 is a compact, fluorescent, flameproof, Wellglass light fitting for use in hazardous areas designated as Zone 1, Zone 2, Zone 21 and Zone 22.

  • Flameproof Wellglass Weight: 5.0 kg | 11.02 lbs
  • Flameproof Wellglass Volume: 35.5 dm³ | 2166.34 in³
  • Cable Entries: 2 x M20 side entries
LED Luminaires Ex d With Diffused Lens Appleton ATX Order Code
E27 lampholder – Incandescent 200 Watts maximum, compact fluorescent 23 Watts, mixed 160 Watts maximum, halogen 150 Watts LDP2M20

dimensions in mm

➡ View our complete range of ATEX Lighting products for Zone 1 & Zone 2 (Zone 21 & 22) hazardous area lighting applications.

TEMPERATURE RATINGS FOR GAS

Lamp Type and Wattage Ambient Temperature
Ta = +40 °C (+104 °F) Ta = +50 °C (+122 °F)
Temperature Rating Cable Entry Temperature Temperature Rating Cable Entry Temperature
°C °F °C °F
18 W Compact Fluorescent T6 T5
20 W Compact Fluorescent T6 T5
25 W Compact Fluorescent T6 T5
70 W Halogen T4 T3 +90 +194
150 W Halogen T4 +85 +185 T3 +95 +203
160 W Mixed T4 +115 +239 T3 +125 +257
100 W Incandescent T4 +115 +239 T3 +125 +257
200 W Incandescent T4 +115 +239 T3 +125 +257

SURFACE TEMPERATURE FOR DUST

Lamp Type and Wattage Ambient Temperature — Ta = +50 °C (+122 °F)
Surface Temperature Cable Entry Temperature
°C °F °C °F
18 W Compact Fluorescent +85 +185
20 W Compact Fluorescent +85 +185
25 W Compact Fluorescent +85 +185
70 W Halogen +130 +266 +90 +194
150 W Halogen +145 +293 +95 +203
160 W Mixed +145 +293 +125 +257
100 W Incandescent +145 +293 +125 +257
200 W Incandescent +145 +293 +125 +257

 

 ➡ See our technical resource section for further detailed information about hazardous area Zones and T-Class ratings.

ATEX & IECE x Hazardous Area Certifications and Compliances

• Certification Type: Appleton ATX AB14
— Gas: Zone 2 Hazardous Area
– Conforming to ATEX 94/9/CE: II 2 G
– Type of Explosion Protection: Ex d IIC
– T-Rating: See Data Sheet
— Dust: Zone 21 – 22
– Conforming to ATEX 94/9/CE: II 2 D
– Type of Protection: Ex tD A21
• Ambient Temperature: -40 °C to +55 °C (-40 °F to +131 °F)
• CE Declaration of Conformity: 50231
• ATEX Certificate: LCIE 02 ATEX 6053
• Index of Protection according EN/IEC 60529: IP66
• Impact Resistance (shock): IK08
• Internal Volume: > 2 dm3 (122 in³) – 2 litres

other Certifications

  • EURASEC N° TC RU C-FR.ГБ05.B.00912

Hazardous Area Lighting Control Station Plug Junction Box

Lighting | Control Stations | Plugs & Sockets | Junction Boxes | Hazardous Area ATEX Certified Electrical Equipment for Explosive Atmospheres | Zone 1 & Zone 2

Data Sheets