Ex de Explosion Proof Floodlights For Hazardous Areas | Technor FL-25SA

Ex de Lighting - Explosion Proof Hazardous Area Technor FL Floodlight Lighting

Ex de Lighting – Explosion Proof Hazardous Area Lighting

EX De

ZONE 1 & ZONE 21

HAZARDOUS AREA LIGHTING

Floodlights for Zone 1, Zone 21, Zone 2, Zone 22

Technor FL-25SA is an Ex de floodlight suitable for hazardous area lighting with ATEX, IECEx & TRCU certification, ingress protection IP66 and an operational ambient temperature range of -50°C to +55°C.

Also available in an IECEx version with an ambient temperature of -20°C to +60°C.

Light Fitting Specification

Technor FL-25SA Lighting Fixtures & Fittings

  • Product Category: Hazardous Area Lighting
  • Product Range: Floodlights
  • Locations: Zone 1 Hazardous Areas (Gas)
  • Locations: Zone 2 Hazardous Areas (Gas)
  • Locations: Zone 21 Hazardous Area (Dust)
  • Locations; Zone 22 Hazardous Areas (Dust)
  • Explosion Proof/Protection Concept: Ex de (explosion proof) (increased safety)
  • Part Number: Technor FL-25SA
  • Technor Code: A011125111122
  • Power: 250W
  • Floodlight Weight: 23.8kg
  • Temperature Class: T3
  • Type of Explosion Protection: Ex de (explosion proof) (increased safety)
  • Hazardous Area Classification: Zone 1 & Zone 21, Zone 2 & 22, Gas and Dust
  • Marking: II 2 GD Ex de IIB+H2 T(**) Gb Ex tb IIIC T(**) Db IP66

TECHNOR FL LIGHTING – ATEX VERSION

Technor Part Number Code Lamp (W) Lamp Type Weight (kg) Voltage Frequency Ambient Temperature Temperature Class
FL-25SA A011125111122 250W HPS 23.8kg 230V* 50Hz*** -50ºC; +55ºC T3