Increased Safety Junction Boxes | Hazardous Areas Zone 1 2 21 22 | Appleton ATX JBES1218090D3
Appleton ATX JBe10 Increased Safety Junction Boxes
increased safety Junction Boxes
Appleton ATX JBES1218090D3
Zone 1 & Zone 2 (Gas) | Zone 21 & Zone 22 (Dust) Hazardous Areas
The JBES Series are Increased Safety junction boxes, manufactured by Appleton ATX, which are designed to house and protect electrical connections in hazardous areas. They are produced from 316L grade stainless steel, are pre-drilled and come equipped with terminals (including an Earth crossing terminal).
These Increased Safety junction boxes feature smooth, continuously welded seams and hinges supplied on all boxes. They are ideal for use in onshore and offshore wet or corrosive atmospheres such as petroleum refineries, chemical refineries and other industrial process facilities with hazardous area locations according to ATEX or IECEx.
The JBES range is also suitable for use in hazardous area Zone 21 or Zone 22 areas, where flammable dusts are present, either continuously or intermittently such as food processing, dairy, brewing and silos.
- Product: Increased Safety Junction Box
- Manufacturer: Appleton ATX
- Range: JBES
- Increased Safety Junction Box Type: JBe20
- Dimensions Length x Width x Depth: 120 x 120 x 95 mm (4.72 x 4.72 x 3.74 inches)
- Rail Length Capacity: 160 mm (6.30 inches)
- Increased Safety Junction Box Weight: 1.5 kg | 3.31 lbs
- Increased Safety Junction Box Volume: 2.0 dm³ | 122.05 in³
- Ambient Temperature: -50 °C to +70 °C (-58 °F to +158 °F)
- Surface Temperature: T80 °C to T95 °C (T176 °F to T203 °F)
- Hazardous Area Certified: ATEX & IECEx
- ATX JBES1218090D3 is ideal for use in Zone 1 and Zone 21 as well as Zone 2 and Zone 22 hazardous area locations
- Hazardous Area Junction Plugs & Sockets | Hazardous Area Control Stations | Hazardous Area Lighting
Appleton ATX Order Code | Clearance Holes Per Side | ||||
A | B | C | D | ||
Appleton ATX JBES1218090D3 | – | 2 x M20 entries | 3 x M20 entries 1 x M25 entry |
2 x M20 entry |
increased safety junction boxes
dimensions
Factory Drilled Junction Box without Terminal Block (DIN rail supplied)
Appleton ATX JBe20 Dimensions
Maximum Rail Arrangement According to Physical Dimensions
Increased Safety Junction Box Type | Protection | Terminal Size mm² (in²) | Quantity | Maximum Amps |
JBe10 | T6 @ Ta = +55° C (+131 °F) | 2.5 (0.004) 4.0 (0.006) 6.0 (0.009) |
10 8 6 |
16A 25A 32A |
JBe20 | T6 @ Ta = +55° C (+131 °F) | 2.5 (0.004) 4.0 (0.006) 6.0 (0.009) |
21 18 13 |
16A 25A 32A |
Lighting | Control Stations | Plugs & Sockets | Junction Boxes | Hazardous Area ATEX Certified Electrical Equipment for Explosive Atmospheres | Zone 1 & Zone 2
THORNE & DERRICK INTERNATIONAL | ELECTRICAL, MECHANICAL, PROCESS & INSTRUMENTATION | HAZARDOUS AREA & EXPLOSIVE ATMOSPHERES SPECIALISTS