Chromalox HSRL 5-2CT 5W/FT 240V Trace Heating Cables

chromalox-hsrl-hazardous-area-trace-heating-cable-to-150f-65c

Trace Heating Cables

Chromalox HSRL 5-2CT hazardous area trace heating cables are self regulating and provide process temperature maintenance and frost protection to pipework, instrument lines, tanks and drums up to 65º Celsius – with CSA and FM certification Chromalox HSRL heat trace cables ensures operating integrity in Div. 1 hazardous areas.

  • Manufacturer: Chromalox
  • Heating Cable Range: HSRL
  • Heating Cable Code: HSRL 5-2CT
  • Maximum Maintain Temperature : 65° Celsius
  • Maximum Continuous Exposure Temperature : Power Off 85° Celsius
  • Cable Type: Self Regulating, Energy Efficient Trace Heating Cables
  • Cable Ratings: 5 Watts Per Foot @ 50°F
  • Cable Voltage: 240V
  • Maximum Heating Cable Circuit Length: Up to 540 feet
  • Minimum Cable Bend Radius : 1-1/8″
  • Weight/1000′: 66 lbs
  • See Also: Trace Heating

Trace Heating Cable

Construction

Chromalox HSRL Hazardous Area Trace Heating Cable – Construction

  1. Twin 16 AWG Copper Buss Wires are able to Provide reliable electrical current capability.
  2. Semiconductive Polymer Core Matrix is the ‘self regulating component of the cable and it’s electrical resistance varies with temperature.
  3. Polyolefin Jacket is flame retardant and electrically insulates the matric and buss wires and provides resistance to water and some inorganic chemical solutions.
  4. Tinned Copper Braid that provides additional mechanical protection in any environment, and a positive ground path.
  5. High Temperature Fluoropolymer Overjacket  is a corrosion resistant, flame retardant overjacket is highly effective in many environments.

Maximum Circuit Lengths in Feet

Maximum Cable Circuit Length (Ft.) by Start-Up Temperature (°F) and Breaker Size (Amps)
Heating Cable Rating HSRL 5-2CT Trace Heating 
50°F Start-Up (Ft.)
Circuit Breaker



10 A 250
15 A 375
20 A 505
25 A 540
30 A NR
40 A NR
0°F Start-Up (Ft.)
Circuit Breaker


10 A 180
15 A 270
20 A 360
25 A 450
30 A 540
40 A NR
-20°F Start-Up (Ft.)
Circuit Breaker


10 A 160
15 A 245
20 A 325
25 A 405
30 A 490
40 A 540

Hazardous Area Approvals

FM Approvals

  • Class I, Division 1, Groups B, C, D
  • Class II, Division 1, Groups E, F, G
  • Class III, Division 1
  • 3 Watt rated T6 temperature class
  • 5 and 8 Watt rated T5 temperature class
  • 10 Watt rated T4A temperature class

CSA 

  • Class I, Division 1, Groups B, C, D
  • Class II, Division 1, Groups E, F, G
  • 3 Watt rated T6 temperature class
  • 5 and 8 Watt rated T5 temperature class
  • 10 Watt rated T4A temperature class

➡ See also : Electrical Heating for Hazardous Areas

Chromalox SLL Series Long Line Trace Heating Cable - Freeze Protection Of Pipes, Valves & Tanks

Trace Heating Cables & Systems – Design & Supply From Stock

 

Data Sheets