Chromalox SRF 8-2C 240V Self-Regulating Freeze Protection Trace Heating Cable

Chromalox SRF Trace Heating Cable

Trace Heating Cables

  • Manufacturer: Chromalox
  • Heating Cable Range: SRF
  • Heating Cable Code: SRF 8-2C
  • Cable Type: Self-Regulating Freeze Protection Trace Heating Cable
  • Approximate Cable Size : 3/8″ W x 1/8″ H
  • Minimum Cable Bend Radius : 1-1/8″
  • Maximum Continuous Exposure Temperature : Power Off 85° Celsius
  • Output (W.Ft.): 8 Watts @ 50°F
  • Voltage: 240V
  • See Also: Trace Heating

Chromalox SRF 8-2C frost protection trace heating cables provide self-regulating frost protection to institutional buildings and freeze protection applications up to 185º F – with UL listing and CSA certification for fire protection system piping and ordinary areas.

  • Energy efficient SRF frost protection cables requires less energy as less heat is required
  • Simple to install cable and can be cut to any length (see max circuit length)
  • Can be single overlapped without burnout, which simplifies heat tracing of in-line process equipment such as valves, elbows and pumps
  • Field splices can be performed easily in minutes with no scrap or wasted cold sections
  • Chromalox termination, splice, tee and end seal kits reduce installation time

A Twin 16 AWG Copper Buss Wires are able to provide reliable electrical current capability.

B Semiconductive Polymer Core Matrix is the ‘self regulating component of the cable and it’s electrical resistance varies with temperature.

C Fluoropolymer Jacket is flame retardant and electrically insulates the matric and buss wires and provides corrosion resistance.

D Tinned Copper Braid that provides additional mechanical protection in any environment, and a positive ground path.

E High Temperature Fluoropolymer or TPR Overjacket (optional) is a corrosion resistant, flame retardant overjacket is highly effective in many environments. TPR coatings protect against certain inorganic chemical solutions.

Cable Ordering Information

Model Braid and Overcoat Options Output (W/Ft.) Volts Wt./1000′ Chromalox Order Code
SRF 8-2C Standard tinned-copper metallic braid for additional protection and ground path 8 @ 50°F 240V 53 lbs 386994
SRF 8-2CR TPR overjacket over braid for protection against certain inorganic chemical solutions 64 lbs 386070

âž¡ See also : Electrical Heating for Hazardous Areas

Circuit Breaker Selection (Max. Circuit Lengths in Ft.)

Trace Heating Cable Rating 40°F Start-Up (Ft.) 0°F Start-Up (Ft.)
20A 30A 40A 20A 30A 40A
SRF 8-2C 330 420 420 265 395 420

âž¡ Please note thermal magnetic circuit breakers are recommended since magnetic circuit breakers could “nuisance trip” at low temperature.