Hazloc Heaters AEU1 Explosion Proof Electric Air Heater – ATEX IECEx EAC Hazardous Areas

Hazloc Heaters AEU1 Hazardous Area Electric Heater
Explosion Proof Electric Air Heater
AEU1 is an explosion proof hazardous area heater unit manufactured by Hazloc Heaters for providing safe heating suitable for use within ATEX and IECEx rated hazardous areas.
The harsh operating conditions of hazardous area locations require electric heating equipment that is safe, reliable, dependable.
The Hazloc AEU1 range of electric air heaters are designed to provide either primary or supplementary heating for comfort or for freeze protection in areas that are classified by ATEX and IECEx as hazardous locations due to gas or dust atmospheres.
The Hazloc Heaters AEU1 range is available in three sizes all featuring the ExCaliber high performance liquid-to-air heat exchanger cores that are available in twenty-six 230VAC or 400VAC, 50 Hz model choices to meet specific heat output requirements and sixteen 480VAC, 60 Hz models to accommodate shipping vessels, offshore rigs, etc.
Hazloc Heaters AEU1
Explosion Proof Hazardous Area Heater
Product Benefits
The rugged and versatile Hazloc AEU1 incorporates a high quality immersion heater, fan and motor assembly housed within a sturdy 2 mm (14 GA) steel cabinet with epoxy/polyester powder coating for corrosion resistance. As well as a large control enclosure with an extra port for convenient wiring of an external room thermostat, and enclosure O-rings to minimise moisture ingress.
Standard safety features include two temperature high limits and a pressure relief device.
All Hazloc Heaters AEU1 are designed for use in the toughest hazardous area applications.
All cabling used on the AEU1 heater is marine-grade armoured cable and marine-grade cable glands between enclosures.
Hazloc Heaters Aeu1
Key Features of Hazloc AEU1
- Four mounting holes in top panel for dynamic load mounting
- High-quality pressure relief device prevents premature venting
- Stiffened top panel improves mounting strength
- 1″ NPT, main electrical entry shipped with M25 adaptor
- Additional 3/4″ NPT external thermostat entry shipped with certified blanking plug
- Flameproof (Ex d) and dust protected (Ex tb) control box with large opening for easy access to controls
- Epoxy/Polyester coated 2 mm steel cabinet construction for durability
- Automatic and manual high limits in element enclosure housing for added protection
- Flameproof (Ex d) or dust protected (Ex tb) 1500 RPM , 71 frame
- Steel braided flexible control cable and cable glands for secure connections
- O-rings on control & element enclosure lids to minimise moisture ingress
- 3kW model across all voltages
- 230V, 3 Phase, 50 Hz models up to 15 kW are now available
- Bi-metal BTX1-E-A thermostat or electronic XET1-1-E-A thermostat options now available
- Disconnect switch option
- Continuous fan
- Heresite costed core and cabinet options

Hazloc Heaters AEU1 Hazardous Area Heater | Product Benefits
Hazloc Heaters AEU1
Technical Specifications
Hazardous Location Approvals |
ATEX (Gas atmospheres) | SIRA 13 ATEX 1240X CE 2813 Ex II 2G Ex d IIB T4 Gb IP55 (Suitable for Zone 1 and 2) |
-40°C ≤ Tamb ≤ +40°C |
ATEX (Dust atmospheres) 5 mm maximum | SIRA 13 ATEX 1240X CE 2813 Ex II 2D Ex tb IIIB T135°C Db IP65 (Suitable for Zone 21 and 22) |
-30°C ≤ Tamb ≤ +40°C | |
IECEx (Gas atmospheres) | IECEX CSA 13.0034X Ex d IIB T4 Gb IP55 (Suitable for Zone 1 and 2) | -40°C ≤ Tamb ≤ +40°C | |
IECEx (Dust atmospheres) 5 mm maximum | IECEX CSA 13.0034X Ex tb IIIB T135°C Db IP65 (Suitable for Zone 21 and 22) | Without disconnect: -30°C ≤ Tamb ≤ +40°C With disconnect: -20°C ≤ Tamb ≤ +40°C |
|
EAC Ex (Gas atmospheres) | 1Ex d IIB T4 Gb X IP55 (Suitable for Zone 1 and 2) | -40°C ≤ Tamb ≤ +40°C | |
EAC Ex( Dust atmospheres) 5 mm maximum | Ex tb IIIB T135°C Db X IP65 (Suitable for Zone 21 and 22) | -30°C ≤ Tamb ≤ +40°C | |
Cabinet | Cabinet material | 2 mm (14-gauge) steel. Yellow epoxy/polyester powder coated with five-stage pre-treatment, including iron phosphate. | |
Fan guard | Split design with close wire spacing. A 9.5 mm diameter probe will not enter. Black polyester powder coated. | ||
Louvre blades | Anodised extruded aluminium. | ||
Fasteners | Zinc plated steel for corrosion resistance. | ||
Enclosure | Flame proof (Ex d) and dust protected (Ex tb) cast aluminium with O-ring. | ||
Mounting holes | 14 mm diameter holes – Four located on the top face of heater. | ||
Motor/Fan | Motor type | Flameproof (Ex d) or dust protected (Ex tb), thermally protected, 1500 RPM (nominal) permanently lubricated ball bearing type with 71 frame and “easy-off” fan blade replacement feature. | |
Fan | Three-blade non sparking aluminium, steel spider and hub with 14 mm bore. | ||
HeatExchanger | Heating elements | Long-life, low watt-density, high grade metal-sheathed. | |
Heat transfer fluid | Ethylene glycol and water including corrosion inhibitors. | ||
ExCaliberTM Core | Carbon steel headers and element housing with O-ring. Fin tubes are carbon steel tubes with copper-free, roll-formed aluminium fins @ 2.5 mm pitch. Vacuum sealed. Coated with black, high-heat enamel. | ||
Protection | Temperature high limits | One automatic reset rated for 100,000 cycles, and one manual reset. Both are snap-action bi-metal type, open on temperature rise. | |
Pressure relief | High-quality stainless steel pressure relief device. | ||
Controls | Control circuit | Built-in 24VAC control. (1.04 amps, 25VA, grounded) | |
Control contactor | 40 FLA amp (50 A resistive per pole) Definite Purpose. Rated for 500,000 mechanical operations. | ||
Control transformer | Multitap primary, 24VAC secondary. | ||
Fuse protection | Thermal delay fuse with spare, .25” x 1.25” , 24VAC = 1A. | ||
Room thermostat with lockable temperature dial (option code T1 or T2) | Built-in, BTX1-E-A bi-metal (T1) or XET1-1-E-A (T2) electronic explosion-proof thermostat, 5°C to 25°C (40°F to 80°F). Marine-grade armoured cable and cable glands between enclosures. Wall mount thermostats also available – Contact T&D. | ||
Load Isolation |
Disconnect switch with lockable handle (option code D2 or D4) |
Built-in CEAG 20 Amp (D2) or 40 Amp (D4) disconnect switch with lockout feature. Built-in disconnect switch is shipped with a prebuilt gland/cable assembly that must be installed and inspected on site. | |
Additional Options |
Continuous fan (option code F) | Continuous fan operation. Circulates air and prevents gas pockets from forming. | |
Heresite Coating(option code H1, H2, H3) | H1 = Heresite core; or H2 = Heresite cabinet (includes louvres & fan blade); or H3 = Heresite core and cabinet. Note: contact T&D for Heresite lead time. | ||
Operating Limits |
Ambient temperature | Operation: refer to above Hazardous Location Approvals. Storage: -50°C to 60°C. | |
Maximum altitude | 3000 m above sea level. |

Shipping Vessel & Offshore Rig Heaters
AEU1 EXPLOSION PROOF ELECTRIC air HEATER
PRODUCT SPECIFICATION
Hazloc AEU1 specifications for all 50 Hz models by size
Model | AEU1-12 | AEU1-16 | AEU1-20 | ||||||
Fan Diameter in (mm) | 12 (305) | 16 (406) | 20 (508) | ||||||
Nominal kW | 3 | 5 | 7.5 | 10 | 15 | 20 | 25 | 30 | |
Air Delivery m3/hr | 595 | 680 | 1019 | 1359 | 2039 | 2888 | 3568 | 5097 | |
Approx. Air Velocity m/s | 2.1 | 2.4 | 3.6 | 4.9 | 4.1 | 5.8 | 4.6 | 6.6 | |
Approx. Horizontal Air Throw m | 3.9 | 4.6 | 6.7 | 9.1 | 10.1 | 14.0 | 12.5 | 18.6 | |
Motor Power kW (HP) | 0.37 (½) | ||||||||
Max. Mounting Height m (to underside of heater) | 2.1 | 2.1 | 2.3 | 2.9 | 3.0 | 3.4 | 3.6 | 4.6 |
AEU1 Explosion Proof Electric Heater
Product Specification
Hazloc AEU1 specifications for all 60 Hz models by size
Model | AEU1-12 | AEU1-16 | AEU1-20 | ||||||
Fan Diameter in (mm) | 12 (305) | 16 (406) | 20 (508) | ||||||
Nominal kW | 3 | 5 | 7.5 | 10 | 15 | 20 | 25 | 30 | |
Air Delivery m3/hr | 714 | 815 | 1225 | 1630 | 2445 | 3465 | 4280 | 6115 | |
Approx. Air Velocity m/s | 2.2 | 2.9 | 4.3 | 5.9 | 4.9 | 7.0 | 5.5 | 7.9 | |
Approx. Horizontal Air Throw m | 4.7 | 5.5 | 8.0 | 11.0 | 12.1 | 16.8 | 15.0 | 22.3 | |
Motor Power kW (HP) | 0.37 (½) | ||||||||
Max. Mounting Height m (to underside of heater) | 2.1 | 2.1 | 2.3 | 2.9 | 3.0 | 3.4 | 3.6 | 4.6 |

Hazardous Area Electrical Heaters – Hazloc XEU1
Hazloc HEATERS
FOR HAZARDOUS AREA & industrial heating
Hazloc Heaters range of Industrial grade and ATEX, IECEx and CSA certified electrical heating equipment include – Hydronic High Performance Heater (HHP2), Hydronic Unit Heater (HUH2) and Explosion-Proof Electrical Heaters (XEU1 AEU1).
380V, 440V and 480V electric heaters are available in 50 Hz – 60 Hz frequency models and suitable for steam, hot water, glycol or other fluid circulating heating systems.

Hazloc Heaters – Hazardous Area Electrical Heating Equipment (ATEX IECEX CSA)
HAZARDOUS AREA HEATING APPLICATIONS

Mud Tank Building, Boiler Packages, Service Rigs, Drilling Rigs, Paint Spray Booths, Offshore Cabins & Containers.