Ex q Powder Filling
The Ex q Powder Filled Standard of explosion protection states that all equipment that has the potential to arc is contained within an enclosure filled with quartz or glass powder particles. This powder filling prevents the possibility of an ignition. When the enclosure is filled with the powder-type medium (quartz sand, powder or glass beads) there must be no voids within the enclosure.
The hazardous area enclosure construction requirements are a pressure test of 0.5 bar (1 bar = 14.5 psi)Â overpressure for 1 minute and, if not protected by another enclosure, a minimum ingress protection of IP54. If the components are protected by another enclosure, for example, a capacitor with the Ex q type of protection built into a light enclosure, then no specific requirements for the type of ingress protection are required.
Equipment using this Powder Filled explosion protection method is suitable for use in both Zone 1 and Zone 2 hazardous areas.
Explosion Protection Principle
By filling the enclosure with a finely grained powder, an arc within the enclosure is unable, with correct use, to ignite the explosive atmosphere outside. There must be no risk of ignition by flames, nor by increased temperatures at the surface of the enclosure.
Important Design Parameters
- The Ex q filling such as sand, glass balls etc. has to fulfill specific requirements, as must the design of the enclosure
- The powder filling medium must not be able to leave the enclosure, neither during normal operation, nor as the result of electric arcs or other processes inside the powder-filled enclosure
Ex q Powder Filled Applications
Capacitors, electronic assembly groups or transformers which are used in a potentially explosive atmosphere. Often components where sparks or hot surfaces occur but whose functioning is not affected by the finely grained filling.
TYPE OF PROTECTION TO ELECTRICAL EQUIPMENT
Type of Explosion Protection | Powder filling Ex q – EN IEC 60079-5 |
Explosion Protection Principles | Protection principle prevents propagation of flames using an enclosure |
Flammable Material | Gas/vapour (G) |
Category 1 EPL a – Very High Level of Explosion Protection | – |
Category 2 EPL b – High Level of Explosion Protection | Ex q Explosion Protection |
Category 3 EPL c – Normal Level of Explosion Protection | – |
Explosive Atmospheres &
Explosion Protection Concepts
💡 Thorne & Derrick, Specialist Suppliers & Stockists of Electrical and Process Instrumentation Equipment for installation in hazardous area location can assist with your project requirements. Know your Ex Concepts:
- Ex i Intrinsic Safety | Explosive Atmospheres & Explosion Proof Protection Concepts
- Ex d Flameproof | Explosive Atmospheres & Explosion Proof Protection Concepts
- Ex m Encapsulation | Explosive Atmospheres & Explosion Proof Protection Concepts
- Ex e Increased Safety | Explosive Atmospheres & Explosion Proof Protection Concepts
- Ex p Pressurised Enclosures | Explosive Atmospheres & Explosion Proof Protection Concepts
- Ex o Oil Immersion | Explosive Atmospheres & Explosion Proof Protection Concepts
- Ex n Reduced Risk | Explosive Atmospheres & Explosion Proof Protection Concepts
➡  For further technical information see | Hazardous Area Zones | Explosive Atmospheres | T Class Ratings
ELECTRICAL & PROCESS INSTRUMENTATION EQUIPMENT
FOR EXPLOSIVE ATMOSPHERES
Ex q Powder Filled Equipment
Thorne & Derrick are Specialist Distributors of Hazardous Area & Explosion Proof Equipment with IECEx & ATEX Certifications to the onshore and offshore oil, gas, petrochemicals and process industries.
Key Product Categories: Control Panels | Plugs & Sockets | Isolators | Enclosures & Junction Boxes | Lighting | Control Stations | Motor Starters | Heat Trace Cables & Systems | Gas Detection & Detectors | Fire Detection & Detectors | Heat Detectors | Electrical Heating & Heaters
Also Process Instrumentation Products: Ashcroft Pressure Gauges | ASCO Valves | Katronic Flow Meters | KROHNE Flow Meters | VEGA Level Sensors | Rotronic Temperature & Humidity Sensors | SIKA Pressure Gauges

Trace Heating | System Design & Supply