Exd Exe Compound Stopper Box | Hazardous Area | Flameproof & Increased Safety

Raxton Exd/Exe Compound Stopper Box

Electrical Thread Conversions & Cable Installation Solutions for Hazardous Areas & Explosion Proof/Protection Applications

Exe Exd Compound Stopper Box

Flameproof & Increased Safety Compound Stopper Box

ATEX

Adaptors | Flameproof & Increased Safety

Raxton Exd/Exe Compound Stopper Box for hazardous areas is designed to seal conductors at the entry to the enclosure via conduit or to enable an existing compression gland to be converted to a barrier gland. This is achieved by forming a barrier between the individual insulated conductors within the cable to prevent an explosion within the enclosure. The Exd/Exe Compound Stopper Box, manufactured by Raxton, allows compound to be packed around individual insulated conductors. Assembly of the component compresses the packing material and distributes the compound evenly to effect a barrier at point of entry into the enclosure. The flameproof & increased safety Compound Stopper Box is supplied with compound in a pack, complete with making off instructions and gloves. Raxton Compound Stopper Box is marked with the appropriate approval number and size.

Materials

  • Brass: BS2874: 1985 CZ121
  • Stainless Steel: BS970 PT3 316 S11
  • Aluminium: BS1474/1 6082 T4 or T6
  • Aluminium Bronze: BS1400 1985 AB2 or BS2874:1986 CA104

Raxton Exe & Exd stropper boxes are available in a variety of finishes including Nickel, Electro Zinc, Zinc Passivated, Chromatised, Electroless Nickel and Anodised.

Exd exe compound stopper box dimensions

The ATEX Certified swivel adaptors are suitable for both Zone 1 & Zone 2 hazardous area installations.

Thread Bore MN (mm) Thread Length (mm) Protrusion (mm)
M16 7.2 15.0 32.0
M20 12.5 15.0 34.5
M25 18.3 15.0 34.5
M32 24.3 15.0 34.5
M40 30.0 17.0 35.0
M50 41.6 17.0 37.0
M63 53.3 17.0 37.0
M75 65.0 17.0 37.0

Hazardous Areas

The hazardous area compound stopper boxes are certified and approved to the following international hazardous area classifications and are Flameproof & Increased Safety Standards.

Approvals & Certifications: Sira 00ATEX1073U | ITS12ATEX17707X | IECEx ITS12.0079X | GOST TС С-GB.ГБ06.В00105

stopper box Thread selection

These stopper box selection tables identify the standard thread variations produced and are designed to assist the user in selecting the correct hazardous area Exe/Exd stopper box suitable for use in Zone 1 or Zone 2 potentially explosive atmospheres according to the ATEX Directive. 

Isometric to BS 3643:1981

Adaptor Size Major Diameter (mm) Threads per Inch Pitch
16mm (M16) 16 16.93 1.50
20mm (M20) 20 16.93 1.50
25mm (M25) 25 16.93 1.50
32mm (M32) 32 16.93 1.50
40mm (M40) 40 16.93 1.50
50mm (M50) 50 16.93 1.50
63mm (M63) 63 16.93 1.50
75mm (M75) 75 16.93 1.50

 

National Pipe Thread to ANSI/ASME: 1983

Adaptor Size Major Diameter (mm) Threads per Inch Pitch
1/8″ NPT 10.30 27 0.94
1/4″ NPT 13.72 18 1.41
3/8″ NPT 17.15 18 1.41
1/2″ NPT 21.34 14 1.81
3/4″ NPT 26.67 14 1.81
1″ NPT 33.40 11 1/2 2.20
1 1/4″ NPT 42.16 11 1/2 2.20
1 1/2″ NPT 48.26 11 1/2 2.20
2″ NPT 60.33 11 1/2 2.20
2 1/2″ NPT 73.03 8 3.175
3″ NPT 88.90 8 3.175
4″ NPT 114.30 8 3.175

 

British Standard Pipe to BS 21:1985

Adaptor Size Major Diameter (mm) Threads per Inch Pitch
1/8″ BSP 9.73 28 0.91
1/4″ BSP 13.16 19 1.34
3/8″ BSP 16.66 19 1.34
1/2″ BSP 20.96 14 1.81
3/4″ BSP 26.44 14 1.81
1″ BSP 33.25 11 2.31
1 1/4″ BSP 41.91 11 2.31
1 1/2″ BSP 47.80 11 2.31
2″ BSP 59.61 11 2.31
2 1/2″ BSP 75.18 11 2.31
3″ BSP 87.88 11 2.31
4″ BSP 113.03 11 2.31

 

Adaptors, Reducers, Stopping Plugs & Breather Drains

For further information about the complete range of Raxton electrical thread conversion and flameproof/increased safety products for use with cables and ATEX electrical enclosures installed in potentially explosive atmospheres or hazardous area locations please refer to the information below:

Exd/Exe Reducers Exd/Exe Male to Male & Female to Female Adaptors Exd/Exe Right Angle Adaptors
Exd/Exe Swivel Adaptors Exd/Exe Y and T Adaptors Exd/Exe Stopping Plugs
Exd/Exe Breather Drains Exd/Exe Compound Stopper Box Exd/Exe Unions

 

➡ View all Exd Exe Adaptors, Reducers, Stopping Plugs & Breather Drain Plugs | ATEX Hazardous Area

Hazardous Area ATEX

Exd Exe Adaptors, Reducers, Stopping Plugs & Breather Drain Plugs | ATEX Hazardous Area

THORNE & DERRICK

Thorne & Derrick are Specialist Distributors of Hazardous Area & Explosion Proof Equipment with IECEx & ATEX Certifications to the onshore and offshore oil, gas, petrochemicals and process industries.

We supply major UK and international infrastructure projects and also MRO (Maintenance, Repair, Operations) requirements for both planned and unplanned plant shutdowns – we react with a rapid response to customer demand to ensure downtime is minimised and reliable Power, Light & Heat is restored or provided.

Key Product Categories: Control Panels | Plugs & Sockets | Isolators | Enclosures & Junction Boxes | Lighting | Control Stations | Motor Starters | Heat Trace Cables & Systems | Gas Detection & Detectors | Fire Detection & Detectors | Heat Detectors | Electrical Heating & Heaters 

➡ Also Process Instrumentation Products: Ashcroft Pressure Gauges | ASCO Valves | Katronic Flow Meters | KROHNE Flow Meters | VEGA Level Sensors | Rotronic Temperature & Humidity Sensors | SIKA Pressure Gauges

Hazardous Area Electrical Equipment