Ex de Lighting – Explosion Proof Hazardous Area Technor RMS 560 Fluorescent Lighting

View Sub Products

Ex de Lighting - Explosion Proof Hazardous Area Technor RMS 560 Fluorescent Lighting

Ex de Lighting – Explosion Proof Hazardous Area Technor RMS 560 Fluorescent Lighting

ZONE 1, ZONE 21 FLUORESCENT LIGHTING

EXPLOSION PROTECTION EX DE

Explosion Proof Fluorescent Lighting for Zone 1, Zone 21, Zone 2, Zone 22 Hazardous Area Lighting Applications

Thorne & Derrick, the Specialist Distributors of Hazardous Area Lighting can provide competitive prices and supply from stock the complete range of Technor products including electrical enclosures and junction boxes.

Technor’s RMS 560 is a fluorescent lighting fixture suitable for hazardous area lighting and offers offers Ex-e IIC mode of protection and has a body and glass frame are made of stainless steel AISI304 and manufactured from a single sheet of steel with no invasive mounting holes, to minimise the risk of water ingress through the housing.

Designed to allow the operator to work with free hands and alone during start-up or maintenance without needing to support any of the Ex de lighting fixture.

Technor EMS 560 Ex de fluorescent lighting fixtures are 95% recyclable only components and insulation of single core wires need some more care.

Technor RMS 560 fluorescent lighting is classified to international hazardous area classifications with ATEX and TRCU certification, with ingress protection IP65 and an operational ambient temperature range of -20°C to +60°C.

Technor RMS 560 Fluorescent Lighting – Technical Features

MaterialAISI304 stainless steel, 0,8mm thickness and transparent part in tempered glass (AISI 316 L version available upon request)
IP ratingIP65 (IP66 on request)
Ambient temperature range-20°C to +60°C
Approvals
INERIS 01ATEX0060 (standard)
TR CU (marking upon request, ordering code to be required)
GasketsSpecial cross-section tightness gasket, silicon rubber made (closed cell), located in housing channel between body and window frame.
EntriesBody complete of two 21mm Ø through holes (on one side) for cable entry, one complete of metallic plug with M20 locknut and gasket and the other one with temporary plastic plug to prevent dust ingress.
Hardware and screwsAISI304 Stainless steel external hardware and screws
LampsRMS series lighting fixtures are suitable for two pins fluorescent lamps G13 socket Philips TL-D or equivalent (lamps excluded)
BallastHigh frequency electronic ballast conforming with EN 60079 – 15 and IEC 60079 – 15
Rated Operation Voltage (UE)220-240 V
Frequency50 – 60 Hz
Power Factor>0.95
Accessories available upon requestPole mounting kit / Ceiling mounting kit / Suspension mounting kit / Wall mounting kit 3°- 4° through holes opposite side
Operating Principles
Available RMS.. lighting fixtures for emergency service of one tube:
– 90 minutes ; guarantees 60’ duration with constant flux (emergency lumen factor 18%) and 30’ with decreasing flux

Technor RMS 560 Lighting – Normal Service

Technor Part NumberCodePower (W)Temperature ClassAmbient TemperatureDimensions (mm)Weight (kg)
ABC
RMS-560-03A0201211803001X18Gas T5 Dust T100ºC(-20º;+55º)**7372391235.60
RMS-560-04A0201221803002X18Gas T5 Dust T100ºC(-20º;+55º)**7372391235.70
RMS-560-01A0201213603001X36Gas T5 Dust T100ºC(-20º;+55º)**13472391238.90
RMS-560-02A0201223603002X36Gas T5 Dust T100ºC(-20º;+55º)**13472391239.10
RMS-560-03/MS*A0201211803011X18Gas T5 Dust T100ºC(-20º;+55º)**7372391235.65
RMS-560-04/MS*A0201221803012X18Gas T5 Dust T100ºC(-20º;+55º)**7372391235.75
RMS-560-01/MS*A0201213603011X36Gas T5 Dust T100ºC(-20º;+55º)**13472391238.95
RMS-560-02/MS*A0201223603012X36Gas T5 Dust T100ºC(-20º;+55º)**13472391239.15

* With micro-switch
** In case of maximum ambient temperature reach +60°C, temperature class changes into T4/T135°C (ordering code to be required).
In case of maximum ambient temperature reach +40°C, temperature class changes into T6/T85°C (ordering code to be required).

Technor RMS 560 Lighting – Emergency Service

Technor Part NumberCodePower (W)Temperature ClassAmbient TemperatureEmergency DurationDimensions (mm)Weight (kg)
ABC
RMS-560-03 LE-P-90A0201211803101X18Gas T5 Dust T100ºC(-20º;+55º)*90′7372391839.50
RMS-560-04 LE-P-90A0201221803102X18Gas T5 Dust T100ºC(-20º;+55º)*90′7372391839.60
RMS-560-01 LE-P-90A0201213603101X36Gas T5 Dust T100ºC(-20º;+55º)*90’**134723912314.10
RMS-560-02 LE-P-90A0201223603102X36Gas T5 Dust T100ºC(-20º;+55º)*90’**134723912314.30

* In case of maximum ambient temperature reach +60°C, temperature class changes into T4/T135°C (ordering code to be required).
In case of maximum ambient temperature reach +40°C, temperature class changes into T6/T85°C (ordering code to be required).
** 120’ version available upon request (ordering code to be required).

Explosion Proof Hazardous Area Technor RMS 560 Fluorescent Lighting - Dimensions

Explosion Proof Hazardous Area Technor RMS 560 Fluorescent Lighting – Dimensions

HAZARDOUS AREA CERTIFICATION & MARKING FOR Lighting

II 2 GD

  • Ex de IIC T(**)
  • Ex tD A21 IP65 T(**)
  • ** T6/T85°C, T5/T100°C, T4/T135°C

under IEC Ex directive, junction boxes and enclosures are suitable for IIC group of gases/dusts only 

Approvals
INERIS 01ATEX0060 (standard) TR CU (marking upon request, ordering code to be required)