Hazardous Area Recessed Fluorescent Ex e Zone 1 ATEX | Abtech LX1XEN236

Zone 1 ATEX - Abtech LX1XEN236 Recessed Fluorescent

Zone 1 ATEX – Abtech LX1XEN236 Recessed Fluorescent

Zone 1 Recessed Fluorescent

Explosion Protection Ex E

Recessed Fluorescent for Zone 1 Hazardous Area Lighting Applications

Thorne & Derrick, the Specialist Distributors of Hazardous Area Lighting can provide competitive prices and supply from stock the complete range of Abtech products including electrical enclosures and junction boxes.

The Abtech LX1XEN236 Ex e recessed fluorescent is designed for use in Zone 1 hazardous areas – part of the Abtech Xena Zone 1 Lighting range.

The Zone 1 Recessed Fluorescent is rated IP54 and both ATEX and IECEx compliant.

  • Product Category: Hazardous Area Lighting
  • Product Range:Recessed Fluorescent Lighting
  • Locations: Zone 1 Hazardous Areas (Gas)
  • Explosion Proof/Protection Concept: Ex e mb (increased safety, encapsulation)
  • Part Number: Abtech Xena LX1XEN236
  • Lamp Type: T8 bi-pin
  • Lamp Cap: G13
  • Power Consumption: 2 x 36W
  • Hazardous Area ATEX Certification Code: CML 14ATEX3105 / IECEx CML 14.0043
  • Type of Protection: Panel – Ex e mb (increased safety, encapsulation)
  • Hazardous Area Classification: Zone 1 Gas
  • Zone 1 Recessed Fluorescent Coding: Panel – Ex ib IIB T4 Gb, Driver – Ex eb [ib Gb] qb IIB T4 Gb
  • Zone 1 Hazardous Area Lighting

âž¡ T&D also offer Abtech Zone 2 Hazardous Area Lighting. Please contact us for more details.

Zone 1 Increased Safety Recessed Fluorescent Hazardous Area ATEX IECEx Ex e – Abtech Xena

Zone 1 Increased Safety Recessed Fluorescent Hazardous Area ATEX IECEx Ex e – Abtech Xena

Abtech Xena Zone 1 Lighting

Luminaire Ratings

Abtech Product Reference Lamp
Type
Lamp
Cap
Power
(W)
Temperature
Rating**
Ambient
Temperature
Weight
(kg)
LX1XEN236 T8 bi-pin G13 2 x 36W T4 -40°C to 55°C 13.1

 

Zone 1 Increased Safety Recessed Fluorescent Abtech Xena - Dimensions

Zone 1 Increased Safety Recessed Fluorescent Abtech Xena – Dimensions

HAZARDOUS AREA CERTIFICATION

Abtech Xena recessed fluorescent lights are certified according to leading hazardous area classifications including:

  • Hazardous Area Classification Zone 1 Gas
  • Type of Explosion Protection Ex e mb (increased safety, encapsulation)
  • Apparatus Coding Standard: II 2 G Ex e mb II T4 Gb / With Isolator: Ex d e mb IIC T4 Gb
  • Certificate Number CML 14ATEX3105 / IECEx CML 14.0043