Ex e Junction Boxes – Increased Safety Hazardous Area Technor AQ-AR ALU High Thickness Junction Boxes

Ex e Junction Boxes - Increased Safety Hazardous Area Technor AQ-AR ALU High Thickness Junction Boxes

Ex e Junction Boxes – Increased Safety Hazardous Area Technor AQ-AR ALU High Thickness Junction Boxes

Technor AQ-AR ALU High Thickness is a hazardous area junction box which offers Ex-e IIC mode of protection and is suitable for use in hazardous areas and chemical agents environments, sea water corrosion resistance and extreme low and high temperatures.

Technor AQ-AR ALU High Thickness are classified to international hazardous area classifications with ATEX certification, with ingress protection IP65 and an operational ambient temperature range of -50°C to +60°C.

AQ-AR ALU High Thickness junction boxes are used to house Ex e and Ex i terminals and the maximum number of terminals change on the base of the terminals section, enclosure operating temperature and the required temperature class.

The EFE prefix is used for Ex de push button station execution and enclosure can be equipped with:

  • Standard and emergency push buttons;
  • Selector switches;
  • Pilot lights;
  • Measurement instruments;
  • Electric and electronic equipment Ex de certified.

Technor AQ-AR ALU High Thickness Junction Box – Technical Features

Material Aluminium with low content of copper
IP Rating IP65
Ambient Temperature Range -50°C to +60°C
Approvals
IMQ 08 ATEX 028X
TR CU
Standard Certificate Label Made by self adhesive UV and corrosion resistant polyester, approved by INERIS Laboratory.
Surface Treatment Green colour polyurethane painting cycle RAL6003 (other colour available upon request)
Entries Metric pitch 1.5, ANSI B1.20.1 NPT, UNI-6125
Hardware & Screws AISI304 Stainless steel
Accessories Available Upon Request
Hinges
Drain/breather valve
Traffolyte/Stainless steel certificate label
Internal mounting plate
Passing through earth bolt.

Technor AQ-AR ALU High Thickness Junction Box – Aluminium

Technor Part Number Dimensions Weight (kg)
A B C D E
AR-8A AL S 330 660 177 305 635 16.7
AR-8A AL L 580 840 205 560 810 36
AR-8A AL (HTH) 495 495 171 470 470 17.3
AR-8 AL (HTH) 330 495 171 320 470 12.4
AR-8 AL A (HTH) 332 332 178 310 315 8

 

Increased Safety Hazardous Area Technor AQ-AR ALU High Thickness Junction Boxes - Dimensions

Increased Safety Hazardous Area Technor AQ-AR ALU High Thickness Junction Boxes – Dimensions

HAZARDOUS AREA CERTIFICATION & MARKING FOR ENCLOSURES

II 2 GD

  • Ex e IIC Gb / Ex ia Ga IIC T(**)
  • Ex tb IIIC T(**) Db IP66
  • ** T6/T85°C, T5/T100°C, T4/T135°C

under IEC Ex directive, junction boxes and enclosures are suitable for IIC group of gases/dusts only 

 

Data Sheets