Chromalox SRP 15-2C 15W/FT 208V – 277V Trace Heating Cables

chromalox-srp-self-regulating-trace-heating-cable-temperature-230f-110c

Trace Heating Cables

  • Manufacturer: Chromalox
  • Heating Cable Range: SRP
  • Heating Cable Code: SRP 15-2C 15W/FT 208V – 277V
  • Maximum Maintain Temperature : 110° Celsius
  • Maximum Continuous Exposure Temperature : Power Off 135° Celsius
  • Cable Type: Self Regulating Trace Heating Cables
  • Cable Ratings: 15 Watts Per Foot @ 50°F
  • Cable Voltage: 208V – 277V
  • Maximum Heating Cable Circuit Length:  500 Foot
  • See Also: Trace Heating

SRP trace heating cables manufactured by Chromalox, including SRP 15-2C, provide frost protection to pipework and valves, tanks and associated mechanical services – suitable for hazardous area zones including Div 2 and ATEX Zone 1.

➡ See also : Electrical Heating for Hazardous Areas

Heating Cable Applications

  • Process Pipework Maintenance
  • Frost Protection of Pipework
  • Fluid Flow, Transfer & Viscosity Maintenance

Chromalox SRP Self-Regulating Trace Heating Cable

 

  1. Twin 16 AWG Copper Buss Wires are able to provide reliable electrical current capability.
  2. Semiconductive Polymer Core Matrix is the self regulating component of the cable and it’s electrical resistance varies with temperature.
  3. Fluoropolymer Jacket is flame retardant and electrically insulates the matrix and buss wires and provides corrosion resistance.
  4. Tinned Copper Braid that provides additional mechanical protection in any environment, and a positive ground path.
  5. High Temperature Fluoropolymer Overjacket (optional) is a corrosion resistant, flame retardant overjacket which is highly effective in many environments. It protects against exposure to organic or corrosive solutions as well as abrasion and impact damage.

Cable Ordering Information

Output (W/Ft.)VoltsModelCable ConstructionStockChromalox Part CodeWt./1000′ (lbs)
Output at Rated Voltage
15 @ 50°F208 – 277SRP 15-2 CBraid OnlyS38711068
SRP 15-2CTStandard Braid and overjacket38713780

Circuit Breaker Selection

Maximum Cable Circuit Length (Ft.) by Start-Up Temperature (°F) and Breaker Size (Amps)
Heating Cable RatingSRP 15-2CT Trace Heating Cable
50°F Start-Up (Ft.)
15 A150
20 A195
30 A295
40 A390
50 A500
0°F Start-Up (Ft.)
15 A120
20 A160
30 A235
40 A320
50 A400
-20°F Start-Up (Ft.)
15 A110
20 A145
30 A220
40 A290
50 A360

 

Chromalox SLL Series Long Line Trace Heating Cable - Freeze Protection Of Pipes, Valves & Tanks