Chromalox SRP 5-1C 5W/FT 120V Trace Heating Cables

chromalox-srp-self-regulating-trace-heating-cable-temperature-230f-110c

Trace Heating Cables

  • Manufacturer: Chromalox
  • Heating Cable Range: SRP
  • Heating Cable Code: SRP 5-1C 5W/FT 120V
  • Maximum Maintain Temperature : 110° Celsius
  • Maximum Continuous Exposure Temperature : Power Off 135° Celsius
  • Cable Type: Self Regulating Trace Heating Cables
  • Cable Ratings: 5 Watts Per Foot @ 50°F
  • Cable Voltage: 120V
  • Maximum Heating Cable Circuit Length:  490 Foot
  • See Also: Trace Heating

SRP trace heating cables manufactured by Chromalox, including SRP 5-1C, provide frost protection to pipework and valves, tanks and associated mechanical services – suitable for hazardous area zones including Div 2 and ATEX Zone 1.

➡ See also : Electrical Heating for Hazardous Areas

Heating Cable Applications

  • Process Pipework Maintenance
  • Frost Protection of Pipework
  • Fluid Flow, Transfer & Viscosity Maintenance

Chromalox SRP Self-Regulating Trace Heating Cable

 

  1. Twin 16 AWG Copper Buss Wires are able to provide reliable electrical current capability.
  2. Semiconductive Polymer Core Matrix is the self regulating component of the cable and it’s electrical resistance varies with temperature.
  3. Fluoropolymer Jacket is flame retardant and electrically insulates the matrix and buss wires and provides corrosion resistance.
  4. Tinned Copper Braid that provides additional mechanical protection in any environment, and a positive ground path.
  5. High Temperature Fluoropolymer Overjacket (optional) is a corrosion resistant, flame retardant overjacket which is highly effective in many environments. It protects against exposure to organic or corrosive solutions as well as abrasion and impact damage.

Cable Ordering Information

Output (W/Ft.) Volts Model Heating Cable Construction Stock Chromalox Part Code Wt./1000′ (lbs)
Output at Rated Voltage
5 @ 50°F 120 SRP 5-1C Braid Only S 387161 68
SRP 5-1CT Standard Braid and Overjacket 387188 80


Circuit Breaker Selection

Maximum Cable Circuit Length (Ft.) by Start-Up Temperature (°F) and Breaker Size (Amps)
Heating Cable Rating SRP 5-1C & SRP 5-1CT Trace Heating Cable
50°F Start-Up (Ft.)
15 A 145
20 A 195
30 A 295
40 A 390
50 A 490
0°F Start-Up (Ft.)
15 A 110
20 A 145
30 A 215
40 A 295
50 A 360
-20°F Start-Up (Ft.)
15 A 70
20 A 90
30 A 135
40 A 180
50 A 225

 