Constant Wattage Heat Tracing | Eltherm ELKM-AS Heat Tracing Cable up to 260°C

Eltherm ELKM-AS Constant Wattage Heat Tracing Cable


Constant Wattage heat tracing cables

ATEX Heat Tracing Cable | Eltherm ELKM-AS

Eltherm ELKM-AS constant wattage heat tracing cables provide process temperature maintenance and frost protection to pipework, instrument lines, tanks and drums up to 260° Celsius.

These heat tracing cables manufactured by Eltherm offer flexibility in use as they can easily be cut to the required length off the roll, with the assurance of constant power output. There is no need for connecting cable and input can be unilateral. The constant wattage heat tracing cable is quick and easy to assemble, saving time and reducing operating costs.

Eltherm resistance heating cables are manufactured from a high-resistance heating conductor, PTFE insulated with protective braid and fluoropolymer outer jacket. Powered at specific voltage the resistance heat generated by the conductors provides electrical trace heating to pipes and vessels. Resistance heating cables will “burn-out” if overlapped unlike self-regulating trace heating cables.

Since the heat tracing cable output of up to 30 W/m is possible for lengths laid to piping, Eltherm ELKM-AE heat tracing cables are particularly suited for piping with high output requirements such as in industrial process technology. The following are applications are below:

  • Silos, vessels, tanks
  • Valves, pumps
  • Pipelines
  • Industrial Applications
  • Rotor blade tips

Eltherm ELKM-AS resistance heating cables and tapes provide process temperature maintenance and frost protection to vessels, pipes, valves and small components up to 260° Celsius.


HEAT TRACING Resistance CABLES

ELTHERM ELKM-AS SPECIFICATION

  • Nominal Supply Voltage : 750V
  • Maximum Output : 30 w/m
  • Maximum Operating Temperature : 260ºC
  • Minimum Installation Temperature : -60° Celsius
  • Minimum Heater Cable Bend Radius : 2.5mm x outer diameter
  • Insulation : PTFE
  • Protective Braid: Nickel-plated Copper
  • Heat Conductor : Stranded, spirally wound for nominal resistance > 8,000Ω/km
  • Moisture Proof : Yes
  • Manufactured According To : DIN VDE 0253
  • Heating Cable Type : Resistance heating cable

Eltherm ELKM-AS Heat Tracing Cable

  1. Heating conductor: stranded or spirally wound
  2. Insulation: Fluoropolymer
  3. Protective braid: Nickel plated copper

Eltherm ELKM-AS Heating cable Benefits

  • Highly flexible
  • Small bending radius
  • High operating temperature
  • High chemical resistance
  • Moisture proof

ELKM-AS


resistance Heating Cables – Eltherm ELKM-AS

SELECTION TABLE

Contact T&D for technical guidance, heat loss calculations for pipework systems and optimum specification of the correct trace heater cable for your application.

Resistance heating cable application : frost protection and process heating.

Nominal Resistance Ω/km Cable Outer Diameter Approx (mm) Weight Approx (g/m) Temperature Coefficient (x 10-3/K) Eltherm Order Code
1.95 (Cu 10mm²) 7.11 157.0 4.30 0137000
2.90 (Cu 6mm²) 5.99 104.9 4.30 0137002
4.40 (Cu 4mm²) 4.73 69.8 4.30 0137004
7.20 (Cu 2.5mm²) 3.89 48.3 4.30 0137007
10.00 3.62 40.6 4.30 0137009
11.70 (Cu 1.5mm²) 3.53 37.6 4.30 0137010
15.00 3.20 33.6 4.30 0137012
25.00 3.15 31.1 3.00 0137016
31.50 3.55 38.6 1.60 0137020
50.00 3.15 31.1 1.60 0137030
65.00 3.04 28.6 1.60 0137032
80.00 3.32 34.5 0.90 0137038
100.00 3.11 31.0 0.90 0137042
157.00 3.10 31.2 0.45 0137045
180.00 2.84 25.8 0.90 0137052
200.00 2.98 28.2 0.45 0137054
260.00 2.87 26.3 0.45 0137058
280.00 2.76 24.3 0.38 0137060
328.00 3.13 30.6 0.18 0137061
360.00 2.71 23.7 0.45 0137064
430.00 2.96 27.6 0.18 0137266
480.00 2.94 26.8 0.18 0137069
600.00 2.80 24.9 0.18 0137213
800.00 2.69 23.2 0.18 0137080
1000.00 2.81 24.9 0.04 0137082
1470.00 2.64 22.6 0.04 0137214
1750.00 2.66 22.3 0.04 0137094
1900.00 2.84 25.6 0.40 0137215
2900.00 2.68 23.1 0.40 0137219
4000.00 2.61 21.9 0.40 0137114
4700.00 2.55 21.6 0.15 0137118
6000.00 2.49 20.6 0.20 0137237
7000.00 2.43 19.9 0.15 0137126
8000.00 2.41 19.7 0.15 0137128

Eltherm ELKM-AS resistance heating cables for frost protection up to nominal resistances up to 1,500,000Ω/km available on request.


Eltherm Heated Hoses

Bespoke Heated Hose Designs | 40+ Years Experience from Process Heating Specialists | CONTACT US

Data Sheets